Water Source Application Water Source Application Water Source - - PowerPoint PPT Presentation
Water Source Application Water Source Application Water Source - - PowerPoint PPT Presentation
Water Source Application Water Source Application Water Source Application & Competitor Comparison & Competitor Comparison & Competitor Comparison Content Water Source Product Selection Water Source Product Selection
- Water Source Product Selection
Water Source Product Selection
- Piping Sizing
Piping Sizing
- Water Cooler
Water Cooler
- Competitor Comparison
Competitor Comparison
Content
Selection Criteria?
- 1. Capacity required, Total Cooling (TC), Sensible Cooling (SC)
- 2. Entering Air Temperature, DB/ WB
- 3. Entering/ Leaving Water Temperature, EWT/ LWT
- 4. Airflow required, CFM
- 5. Static pressure, Ps
- 5. Water Flowrate, l/s
Water Source Product Selection
Entering Air Temperature, i. Entering Dry Bulb, EDB ii. Entering Wet Bulb, EWB Tip: DB changes while WB remains will not affect the TC. SC2(kW)= SC1(kW)+ [1.23* (l/s)* (1-BPF)* (EDB2-EDB1)/1000] Example: if TC = 3.52kW and SC= 2.78kW at EDB = 27°C, EWB= 19°C. Calculate the TC and SC when EAT is as following; EDB = 30°C, EWB = 19°C Assuming air flow rate = 180 l/s, BPF= 0.06, Water flowrate = 1.25m3/hr
Manual Selection & Calculation
Since WB1 = WB2, then TC1 = TC2 = 3.52kW, and
TC = 3.52kW and SC= 2.78kW EDB = 27°C, EWB = 19°C EDB = 30°C, EWB = 19°C
SC2=SC1+ [1.23*(l/s)*(1-BPF)*(EDB2-EDB1)/1000] = 2.78+[1.23*180*(1-0.06)*(30-27)/1000] = 3.40kW
Manual Selection & Calculation
Selection & Calculation by Selection Software
Download selection software from e-biz.
1. Select model type 2. Select indoor if split type was chosen 3. Chose the fan speed 4. Key in the water flow 5. Key in the on coil temperature and EWT temperature 6. Key in the designed capacity to fulfill the building heating/cooling load requirement. 7. Key in the capacity tolerance (%) 8. Click “Calculate”
Selection & Calculation by Selection Software
Selection Result
- 9. Select the model closest to the capacity requirement
Example of Piping Sizing
- 1. Determine System Water Flow Rate
- DON’T sum up directly the total nominal water flow of each WSHP unit.
- Total System design flow rate is determined by the performance of the
water cooler, where most of them are evaporative type and is very much dependent on the entering air wet bulb temperature.
- Lower flow rate are preferred in areas with
lower wet bulb temperatures. In more humid areas, a higher water flow rate will supply a higher water temperature to water source units, but with a lower differential.
Example of Piping Sizing
- 2. Determine WSHP unit flow rate
- Total Cooling load must be known.
- Diversity Effect must be considered. This is to prevent over sizing water
cooler
Diversity Factor = Block Load / Σ(Peak Load)
- Recommended diversity factor;
- 85% for system up to 40 tons
- 80% for system between 40 and 60 tons
- 75% for system greater than 60 tons
- System diversity will only affect the range of the water cooler.
Example of Piping Sizing
- 2. Determine WSHP unit flow rate (Cont…)
Range of Water Cooler, Rs = Twi – Two Where; Twi = entering water temperature Two = leaving water temperature
- By using diversity factor, D, we can then calculate the avarage
range of the water source units, Rp
Rs = D * Rp
- Where typical value of range are between 5°C to 8°C or equally
9°F to 14.4°F.
Example of Piping Sizing
- 3. Determine individual unit peak cooling load
- By assuming 30% of heat rejection ratio,
Qh = 1.3 * D* Qc
Total heat rejection, Qh Total cooling peak load, Qc
Qh = mw * Cp * (Twi – T wo) Where mw = mass flow rate of water Cp = water specific heat
- By replacing with known constants, we will get these familiar
equations;
Qh = 500 gpm (Twi – T wo)
Example of Piping Sizing
- 3. Determine individual unit peak cooling load (Cont…)
- By having water cooler range, Rs in the equation;
Qh = 500 * gpm * Rs
- By having total peak cooling load, Qc in the equation;
1.3 * D* Qc = 500 * gpm * Rs
- Thus the individual unit peak cooling load, qc
1.3 * qc = 500 * gpm * Rp
Example of Piping Sizing
Example:
A water loop system consists of 30 units of water source heat pump units with a combined total peak loading of 450,000btu/hr. the system is served by a centrifugal water pump. A closed loop water cooler is used to give a leaving water temperature of 30°C. the ambient air wet bulb temperature is 25°C.
- Determine the required total system water flow rate.
From the given table, at 25°C wet bulb temperature, the water flow rate is 2.36 gpm/ton. Therefore, the total system water flow rate is 2.36 gpm/ton * (450000/12000)ton = 88.5 gpm.
- Calculate the average range of the water source units
The system range is first calculated; Rs = 1.3 * D * Qc / gpm / 500 = 1.3 * 0.85 * 450,000 / 88.5 / 500 = 11.24°F or 6.24°F Rp = Rs / D = 13.22°F or 7.35°F
- If one of the water source units has been designed to give a cooling capacity of 11,000btu/hr,
calculate the water flow rate required. Rp = 1.3 * qc / gpm / 500 ⇒ 13.22 = 1.3 * 11000 /gpm/500 ; gpm = 2.16gpm
- Recalculate if there is no diversity factor is applied.
If D = 1, and maintaining the flow rate, Rp = Rs / D = 13.22°F or 7.35°F
Example of Piping Sizing
- 4. Piping Sizing
- Important to ensure the selected water pump is sufficient to deliver the
required water flow rate.
- To do this calculation, it is important that a detailed drawing layout of
all components in the system is available.
- The layout should give dimensional lengths of the piping network.
- Location of water cooler, pumps and boiler must be identified.
- All fittings and accessories used in the piping installation should be
clearly identified.
- Study the pipe circuit layout and do preliminary check if the circuits are
- balanced. Re-arrange if necessary. Use balancing valves only if it is not
possible to have balanced circuits.
- Size the pipes by using the pipe chart. The water velocity should be in
the range of 2 – 9 fps, with a recommended max friction loss of 10 ft of water per 100 ft.
Example of Piping Sizing
- 4. Piping Sizing (Cont…)
- Calculate equivalent pipe length. Include the losses for all the valves
and fittings used. Calculate the total pipe friction loss by using the friction loss value from the pipe chart. Add this with the pressure drop in heat exchangers, water cooler and boiler.
- Select a pump which will match these total system water flow rate and
total head pressure.
Example of Piping Sizing
Example:
The water source units which serve the main building has a total installed cooling capacity of 560,000 btu/hr (peak load). There a altogether 40 sets, with 10 sets for each of the four floors (1st floor to 4th floor). The water source units have been selected based upon the following conditions: Entering air = 25°C DB / 18°C WB Entering water = 32°C All the units are connected to an evaporative water cooler located on top of an adjoining service building outside of the main building. The outside air wet bulb temperature is at 24°C
Example of Piping Sizing
Example: (Cont..)
- 1. Calculate the total system water flow rate.
Total installed capacity = 560,000 btu/hr (46.67 tons) Therefore, the total system water flow rate @ 24°C wet bulb is 2.19 gpm/ton * 46.67 tons = 102.2 gpm.
- 2. Calculate the range (Rs) of water cooler
For 46.67 tons, use diversity factor of 0.80. Rs = 1.3 * D * Qc / gpm / 500 = 1.3 * 0.80 * 560000 / 102.2 / 500 = 11.40°F or 6.3°C.
- 3. Calculate the range (Rp) of water source units.
Rp = Rs / 0.80 = 11.40/0.80 = 14.25°F or 7.9°C.
Example of Piping Sizing
Example: (Cont..)
4. The unit on the 4th floor have been sized to give the following peak loads; By using equation 1.3 * qc = 500 * gpm* Rp, we can then work out the flow rate through each of these units. Let assume that the total system water flow rate is distributed to all the four floors of the main building in this manner.
Example of Piping Sizing
Example: (Cont..)
5. With this, we can no look into the pipe sizing all the way up to 4th floor. Focus is given to determine the route of least favourable which will give the max friction loss to the water
- pump. i.e. all the way to unit q.
Reference is then made to pipe chart to determine a suitable pipe size.
Example of Piping Sizing
Example: (Cont..)
6. Each of the WSHP has fittings as shown in the diagram below: The water pump has been installed in this manner:
Example of Piping Sizing
Example: (Cont..)
Detail of water pipe connection to the evaporative water cooler is as shown below:
Example of Piping Sizing
Example: (Cont..)
- 7. With all these fittings details and pipe lengths, we can now calculate the pipe friction loss from
the water cooler to point q. This is as demonstrated in this summary table.
Example of Piping Sizing
Example: (Cont..)
Type of Water Cooler
- 1. Closed Circuit Cooling Tower
- 2. Open type cooling tower with heat exchanger
- 3. Dry Cooler
Evaporation of Water to cool the condenser Air Cooled
Water Cooler
Terminology
An evaporative equipment that exposes exposes water directly to the water directly to the cooling atmosphere cooling atmosphere, thereby transferring the heat load directly into the air.
Open Cooling Tower
Water Cooler
Terminology
An evaporative equipment that contains two separate two separate fluid circuits fluid circuits. The first is an external external circuit where water is exposed to the atmosphere as it cascades
- ver the tubes of a coil
- bundle. The second is an
internal internal circuit in which the fluid to be cooled circulates inside the tubes of the coil bundle.
Closed Circuit Cooling Tower
Water Cooler
Terminology
Type of mechanical draft tower in which one or more fans are located at the air inlet to force air into the tower.
Forced Draft
Type of mechanical draft tower in which one or more fans are located at the air outlet to induce air through the air inlets
I nduced Draft
Water Cooler
Terminology
In a counter flow cooling tower, the air enters at the base of the tower, flows upwards and interfaces counter currently with the falling hot water.
Counter Flow
In a cross flow cooling tower, the air flows horizontally through the cooling tower and interfaces perpendicularly with the falling hot water.
Cross Flow
Water Cooler
Terminology
The diff between the water temperature leaving the cooing tower and the wet bulb temperature of the cooling air (atmosphere)
Approach
Water Cooler
Terminology
Loss of water from the cooling tower as a result of evaporation of the circulating water;
Evaporation Loss
%E = [Range(°C) * Circulating flow rate (kg/hr) * 100]/600 Where range = the diff between the leaving and entering water temperatures of the cooling tower.
Water Cooler
Terminology
Loss of water from the cooling tower as a result of carry over of minute water droplets scattered about as drifted by the fan.
Drift Loss
The amount of water discharge from the cooling tower to prevent concentration build up of dissolved minerals which may cause the formation of algae or scale.
Blow Down Volume
Water Cooler
Terminology
The amount of water that is required to maintain the water level in the cooling tower basin.
Make Up Water (M% )
M = E + C + B
Water Cooler
“Hybrid” System
Closed Circuit and Open Circuit Tower
Water Cooler
Water Distribution System
- Open Basins
- Large Orifice, 360° Nozzles
- Easily accessed for maintenance
- Basin water level used to balance flow
- 1. Gravity Distribution
- Pressurized systems
- Large Orifice, 180° directional Nozzles
- spray header and branches
- 2. Spray Distribution
Water Cooler
Air Moving
- > 80% is used in HVAC system
- High volume, low static pressure
- High efficiency
- Low energy consumption
- Improve sound ratings
- 1. Axial Fan
- High volume, high static pressure
- High energy consumption
- Quiet operation
- Tight layout requirement
- 2. Centrifugal Fan
- Example, 1500 GPM, 95°F EWT. 85°F LWT, 78°F EWB
- Counter flow centrifugal fan unit requires 60 HP
- Cross flow axial fan unit requires 30 HP
* Axial fan requires less HP than centrifugal fan*
Water Cooler
Cooling Tower Equipment Layout
- Prevent warm air or drift from being introduced into fresh air intakes or
from being carried over populated areas
- Consider the potential for plume
- Note the direction of the prevailing winds
- Ensure adequate supply of fresh air to the air intakes
- Provide adequate space for piping and proper servicing and
maintenance
- Top of the unit discharge must be at least level with the adjacent wall
Water Cooler
Layout Example
- Adjacent to a wall or building
- In an enclosure
- Adjacent t a louvered or slotted wall
Water Cooler
Layout Example
- Correct cooling tower installation when
located adjacent to a building or wall
- Maximum air velocity should no t exceed
300 FPM or 1.5m/s
- Air entry envelope consists of top and
two sides
- Based o 125,900 CFM, an inlet height of
10 feet and an air inlet length of 12 feet, the distance to the wall is ; 125,900/2 = (10+ 10+ 12)D* 300 D = 6.56 feet
Water Cooler
Layout Example
- When cooling towers are positioned with
air inlets facing each other, the distance between cooling towers is 2D
- If 125,900 CFM, an inlet height of 10 feet and an air inlet length of 12
feet, the distance to the wall is ; 125,900* 2/2 = (10+ 10+ 12)D* 300 D = 13.11 feet
Water Cooler
Layout Example
- Maximum air velocity should
not exceed 400 FPM
- Center of the cooling tower
within the enclosure for uniform air flow to the air inlets
- If 125,900 CFM, enclosure size is 30ft * 20ft ;
125,900 = 2* D* 20* 400 D = 7.87 feet
Water Cooler
Layout Example
- Louver must provide at least
50% free area
- Louver air velocity should not
exceed 600 FPM
- Maintain at least 3 ft between
the tower air inlets and the louvered wall.
Water Cooler
Maintenance – Who needs this?
Water Cooler
Maintenance
Maintenance and water treatment are the most neglected regimens of cooling tower operation, and cooing towers are generally the most neglected components in the mechanical system
WHY???
- Remotely located & difficult to access
- Limited maintenance resources
- People, Training & budgets.
Water Cooler
Maintenance
Review major cooling tower system sand their appropriate maintenance regimens:
- Circulating Water
- Fan & Drive
- Fin & Coil
- Air Entry Louvers
- Drift Eliminators
Water Cooler
Maintenance
Reputable manufacturers provide maintenance instructions and check
- sheets. It is best to follow the
manufacturer’s recommendations! ASHRAE Handbook also provides a good general guide.
Water Cooler
Circulating Water System Types
Cross flow tower operation View of water distribution box
Gravity Flow Water Distribution System
Water Cooler
Circulating Water System Types
Closed Circuit Tower Operation View of Pressurized Distribution System & Nozzles
Pressurized Flow Water Distribution System
Water Cooler
Circulating Water System Types
Spray nozzles & water distribution boxes need to be inspected & cleaned
- After start up and
- Monthly thereafter
Regular inspection allows quick treatment and control of corrosion and mechanical failures.
Water Cooler
Circulating Water System Types
Clogged distribution nozzles cause:
- Reduced or mal-distributed water flow = capacity reduction
- HE surface scaling/ fouling = capacity reduction
- Overflowing distribution boxes = water & chemical loss
- Excessive drift = water & chemical loss
- Fan motor over-amping (forced draft) = reduced motor life
Water Cooler
Circulating Water System Types
Suction Strainers:
- Designed to protect pump &
nozzles
- Inspect & clean weekly
- Operating environments laden
with airborne fibrous material ( agricultural, paper, textile processing demand more frequent strainer cleaning)
Water Cooler
Circulating Water System Types
Poor Strainer maintenance leads to :
- Reduced flow = reduced capacity
- Pump cavitations = pump repair cost and objectionable plant noise
- Collapsed strainers = tower repair costs
Water Cooler
Circulating Water System Types
Basin Maintenance :
- Clean and flush monthly
- Inspect and repair corrosion
Accumulated solids ;
- Clog equalizer & bypass lines
- Hide corrosion cells
- Give breeding environment for bio growth
Water Cooler
Circulating Water System Types
Closed Circuit Tower Water Pumps;
- Inspect seals & free rotation
- f shaft monthly.
- Lubricate bearings per motor
manufacturer instructions.
Water Cooler
Circulating Water System Types
Make-up Water and Operating Level Controls; fff Mechanical float valve Electric valve & sensor
Water Cooler
Circulating Water System Types
Set operating level and water supply pressure to manufacturer’s recommendations
- Inspect water level an adjust float monthly
- Inspect valve seals and full shut off monthly
Clean electronic sensing elements as required.
Water Cooler
Circulating Water System Types
- Malfunctioning level control can be costly with water and chemical
loss and even equipment damage.
- Proper water level control is
required for pump priming and Prevention of air entrainment in suction lines.
Water Cooler
Fan & Drive System
The fan system moves the air which cools the water. It is critical to keep the fan system in top operating condition!
- Daily walk around the tower and listen for unusual noises or vibration
- if reasons for vibration are easily detected, (loose belts, loose motor base,
loose bearing locking collars, loose fan or sheave bushings) correct as required.
- if causes of vibration are not easily detected, consult a specialty vibration
analysis contractor.
- Quarterly clean fan of heavy debris (trash, bird droppings, scale) and
inspect the fan and drive components for tight fasteners, missing balance washers & structural integrity.
Water Cooler
Fan & Drive System
- Repair or replace corroded hardware, even the fan if necessary
- Check the mechanical equipment support for cracks and tight hardware
- Check security of fan guards
Water Cooler
Fan & Drive System
Belt Tensioning
- Check 24 hours after start up
- Check monthly thereafter
- 1/2 “ to ¾ ” deflection with
moderate finger pressure at center span of belt. Check manufacturer’s OM guide.
Water Cooler
Fan & Drive System
Lubrication
- Check oil level weekly
- Change oil 500 hours or 4 weeks
after start up.
- Follow gear box OM guide for oil
type and change frequently.
- Recommend synthetic, oxidation
inhibited oil
Water Cooler
Fan & Drive System
Drive Shafts
- Inspect drive shaft and coupling
hardware monthly
- Inspect coupling flex elements for
buckling and fatigue damage. Replace as required.
Water Cooler
Fan & Drive System
Fan Shaft Bearing
Lubrication Schedule
- 1000 hours or 3 months for
induced draft
- 2000 hours or 6 months for forced
draft
- Use water resistant grease
approved by manufacturer
Water Cooler
Fan & Drive System
Motors
- Wire per nameplate and check rotation
- Multi- lead (9,12 wire) motors may be confusing
- Check multi speed motor rotation at both speeds
- Check current draw on start up
- Check operational controls
- Set proper time delay between speed changes
- Set thermostat differentials to limit fan cycling (3-6 starts/ hour)
Water Cooler
Heat Transfer Surface
Open Tower Packing (Fill):
- Scale, solids & bio-fouling restrict
air & water passages.
- Capacity diminishes rapidly with
increased fouling
- Extra weight can damage fill and
structural supports.
Typical fill clogging from bio-films and suspended solids.
Water Cooler
Heat Transfer Surface
Closed Circuit Tower Coil:
- Scale on coil walls is a direct heat
transfer barrier
- Capacity diminishes with
increased fouling.
Water Cooler
Water Cooler Available in the Market
Standard Features:
- forced draft counter flow design cooling
towers with single module capacities from 10 to 100 cooling tons,15-600 GPM
- Seamless Engineered Plastic (HDPE) Shell
Corrosion Proof Construction
- Forward Curved Centrifugal Blower with
totally enclosed Motor.
- Factory Assembled for Simple Installation
15 Year Shell Warranty
- PVC Water Distribution System with Non-
clog Large Orifice Removable Nozzles
- High Efficiency PVC Fill
- Made in the USA
Water Cooler
Water Cooler Available in the Market
Standard Features:
- induced draft counter flow design cooling towers with
single module capacities from 55 to 250 cooling tons
- Seamless Engineered Plastic (HDPE) Shell
- Corrosion Proof Construction
- Direct Drive Fan System
- Totally Enclosed VFD Rated Motors
- Factory Assembled for Simple Installation
- 15 Year Shell Warranty
- Low Pressure Drop Self Propelled PVC Water Distribution
System
- High Efficiency PVC Fill
- Made in the USA
Water Cooler
Water Cooler Available in the Market
Standard Features:
- induced draft counter flow design
cooling towers with single module capacities from 250 to 500 cooling tons single module capacities from 55 to 250 cooling tons
- Seamless Engineered Plastic (HDPE) Shell
- Corrosion Proof Construction
- Direct Drive Fan System
- Totally Enclosed VFD Rated Motors
- Completely Factory Assembled
- 15 Year Shell Warranty
- Low Pressure Drop Self Propelled PVC Water Distribution system
- High Efficiency PVC Fill
- Made in the USA
Water Cooler
Standard Features:
- induced draft counter flow design
cooling towers with single unit capacities from 250 to 2,000 cooling tons
- Corrosion Proof Construction
- Direct Drive Fan System
- Totally Enclosed VFD Rated Motors
- Factory Assembled for Simple Installation
- 15 Year Shell Warranty
- High Efficiency PVC Fill
- Made in the USA
- Seamless Double Wall Engineered Plastic (HDPE) Shell
- PVC Water Distribution System with Non-clog Large Orifice -Removable Nozzles
Water Cooler
W H11B W H12B HW P33 W H15B HW P41
Capacity, btu/hr
11600 12000 11260 14400 13989
Noise Indoor, dBA
42 37 45 41 45
Cooling EER, Btu/hrW
14.67 15.42 12.49 11.43 12.22
Height, inch
9.84 12.8 12.99 13.27 12.99
Width, inch
40.94 40.75 31.1 42.28 31.1
Depth, inch
19.49 19.68 19.09 19.68 19.09
Volume, ft3
4.54 5.94 4.46 6.39 4.46
Air Flow, CFM
380 380 180 470 403 1.5hp 1.2hp
Competitor Comparison
W H20B HW P49 W H25B W H30B HW P78
Capacity, btu/hr
19500 16719 26000 29920 26614
Noise Indoor, dBA
45 45 47 50 59
Cooling EER, Btu/hrW
12.45 12.22 13.68 12.08 11.6
Height, inch
13.9 12.99 13.39 14.57 15.16
Width, inch
46.57 41.34 52.28 51.06 44.68
Depth, inch
21.26 20.08 21.26 29.33 22.24
Volume, ft3
7.96 6.24 8.61 12.63 8.72
Air Flow, CFM
600 540.31 870 940 1017 2hp 3hp
Competitor Comparison
W H 4 0 B W H 5 0 B H W P1 4 0 H W P1 7 5
Capacity, btu/hr
44870 49880 48109 59710
Noise Indoor, dBA
50 51 63 64
Cooling EER, Btu/hrW
11.57 11.12 13 12.22
Height, inch
17.09 17.09 19.29 19.29
Width, inch
54.17 54.17 58.07 58.07
Depth, inch
31.18 31.18 24.02 24.02
Volume, ft3
16.70 16.70 15.57 15.57
Air Flow, CFM
1325 1470 1589 2204 5hp
Competitor Comparison
McQua y Te m pe rzone Te m pe rzone W H 7 0 B H W P2 1 0 H W P2 3 5
Capacity, btu/hr
76460 70287 78817
Noise Indoor, dBA
53 67 67
Cooling EER, Btu/hrW
12.66 13.31 13.31
Height, inch
19.68 21.06 21.06
Width, inch
62.05 62.8 62.8
Depth, inch
33.19 24.02 24.02
Volume, ft3
23.45 18.38 18.38
Air Flow, CFM
1940 2288 2606 8hp
Competitor Comparison
Indoor Unit
CC0 2 0 C MCD5 1 8 DB CC0 2 5 C MCD5 2 4 DB
Outdoor Unit
W SS0 2 0 A W TK5 1 8 W SS0 2 5 A W TK5 2 4
Capacity, btu/hr
19000 18000 22000 24000
Noise Indoor, dBA
38 N/A 40 N/A
Cooling EER, Btu/hrW
11.8 N/A 13.9 N/A
Height, inch
10.28 10.16 10.28 10.16
Width, inch
41.93 37.24 47.24 37.24
Depth, inch
16.18 19.45 16.18 20.91
Volume, ft3
4.04 4.26 4.55 4.58
Air Flow, CFM
700 600 730 800
Price, RM (Variance)
1736 (273.25) 2009.25 1847 (474.80) 2321.8 2.0HP 2.5HP
Competitor Comparison
Indoor Unit
CC0 3 0 C MCD5 3 0 DB CC0 5 0 C MCD0 4 8 DB
Outdoor Unit
W SS0 3 0 A W TK5 3 0 W SS0 5 0 A W TK0 4 8
Capacity, btu/hr
28000 30000 46500 48000
Noise Indoor, dBA
46 N/A 52 N/A
Cooling EER, Btu/hrW
12.01 N/A 12.15 N/A
Height, inch
14.88 10.16 14.88 16.06
Width, inch
36.57 43.23 51.14 43.23
Depth, inch
21.3 20.91 21.3 29.88
Volume, ft3
6.71 5.31 9.38 12.01
Air Flow, CFM
830 1000 1380 1600
Price, RM (Variance)
2497 (226.65) 2723.65 3228 (879.80) 4107.8 3.0HP 5.0HP
Competitor Comparison
Indoor Unit
CC0 6 0 C MCX0 6 0 EB
Outdoor Unit
W SS0 6 0 A W TK0 6 0
Capacity, btu/hr
54000 60000
Noise Indoor, dBA
53 N/A
Cooling EER, Btu/hrW
13.7 N/A
Height, inch
14.88 24.68
Width, inch
59.02 82.09
Depth, inch
21.3 9.02
Volume, ft3
10.83 10.58
Air Flow, CFM
1530 2000
Price, RM (Variance)
3569 (985.30) 4554.3 6.0HP