Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
WATER SOUCE SYSTEM WATER SOUCE SYSTEM WATER SOUCE SYSTEM Technical - - PowerPoint PPT Presentation
WATER SOUCE SYSTEM WATER SOUCE SYSTEM WATER SOUCE SYSTEM Technical - - PowerPoint PPT Presentation
WATER SOUCE SYSTEM WATER SOUCE SYSTEM WATER SOUCE SYSTEM Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Content I
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- I ntroduction to Water Source System
I ntroduction to Water Source System
- General Benefit of Water Source System
General Benefit of Water Source System
- Product Lineup
Product Lineup
- Product (WH, 5WSS, WSS)
Product (WH, 5WSS, WSS)
- Features
Features
- Handset
Handset
- PCB
PCB
- Control Algorithm
Control Algorithm
- Selft
Selft Diagnosis & Troubleshooting Diagnosis & Troubleshooting
- I nstallation
I nstallation
Content
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
INTRODUCTION to Water Source System
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
Introduction:
What is Water Source Heat Pump?
Finned-tube heat exchanger Water inlet Water
- utlet
4 Way Valve Compressor Expansion device Water-to- refrigerant heat exchanger
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- 1. Water Loop Heat Pump System
- 2. Ground Water Heat Pump System
- 3. Surface Water Heat Pump System
- 4. Ground Coupled Heat Pump System
Water Source System Categories
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
Water Loop Heat Pump Water Loop Heat Pump
- Most common configuration
Most common configuration
- Re
Re-
- circulating water loop
circulating water loop
- Cooling tower & boiler
Cooling tower & boiler
Water Source System Categories
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
Ground Water Heat Pump Ground Water Heat Pump
- Ground water from well
Ground water from well
- Drained back to well,
Drained back to well, drain, stream or lake drain, stream or lake
- Stable throughout the year
Stable throughout the year
- Limited by availability of
Limited by availability of water table and aquifers in water table and aquifers in the ground the ground
Water Source System Categories
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
Surface Water Heat Pump Surface Water Heat Pump
- Open or close loop
Open or close loop
- Open
Open – – water being water being returned back to source or returned back to source or drain drain
- Closed
Closed – – water being re water being re-
- circulated in the closed
circulated in the closed loop loop
- Stable throughout the year
Stable throughout the year
Water Source System Categories
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
Ground Coupled Water Heat Pump Ground Coupled Water Heat Pump
- HE is buried into the earth
HE is buried into the earth
- Installation cost is high
Installation cost is high
- Massive & stable thermal capacity
Massive & stable thermal capacity
Water Source System Categories
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
Water Loop Heat Pump System
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
cooling tower cooling tower pumps pumps plate plate-
- and
and-
- frame
frame heat exchanger heat exchanger heat pumps heat pumps water water distribution distribution loop loop boiler boiler expansion expansion tank tank air air separator separator
Water Loop Heat Pump System
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
32 32º ºC C [90 [90º ºF] F] heat pumps in heat pumps in cooling mode cooling mode cooling cooling tower ON tower ON boiler off boiler off
Summer Operation Summer Operation
Water Loop Heat Pump System
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
Winter Operation Winter Operation
heat pumps in heat pumps in heating mode heating mode 16 16º ºC C [60 [60º ºF] F] boiler on boiler on cooling cooling tower OFF tower OFF
Water Loop Heat Pump System
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
Water Loop Heat Pump System
Spring and Fall Operation Spring and Fall Operation
boiler off boiler off
heat pumps in heat pumps in heating mode heating mode heat pumps in heat pumps in cooling mode cooling mode cooling tower cooling tower OFF OFF
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
General Benefits of a Water Source System General Benefits of a Water Source System
- Heat recovery offers energy savings
Heat recovery offers energy savings
- Individual space control
Individual space control
- Performs both cooling and heating
Performs both cooling and heating
- Flexibility
Flexibility – – additional of heat pump additional of heat pump
- Individual tenant metering
- Small amount of floor space required
Small amount of floor space required
- Unit failure does not affect the rest of the system
Unit failure does not affect the rest of the system
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
Product Lineup & Features
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
Package Type
- Horizontal WSHP, WH-B/BR series
- Vertical WSHP, WV-A/AR series
Split Type
- WSS & 5WSS series + Various Indoor
Product Lineup
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
R410A Water Source Split, 5WSS-AR
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
5CCWS 10/ 15/ 20/ 25/ 30/ 40/ 50/ 60 CR 5CCWS 10/ 15/ 20/ 25/ 30/ 40/ 50/ 60 CR 5CCWS 10/ 15/ 20/ 25/ 30/ 40/ 50/ 60 CR 5WMWS 10/ 15/ 20/ 25 GR 5WMWS 10/ 15/ 20/ 25 GR 5WMWS 10/ 15/ 20/ 25 GR 5CKWS 20/ 25/ 30/ 40/ 50 AR 5CKWS 20/ 25/ 30/ 40/ 50 AR 5CKWS 20/ 25/ 30/ 40/ 50 AR 5CKWS 10/ 15/ 20 CR 5CKWS 10/ 15/ 20 CR 5CKWS 10/ 15/ 20 CR
R410A Water Source Split
5WSS – AR Series 5WSS 5WSS – – AR Series AR Series
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- 1. Features
- 1. Features
1.1 Product Information 1.1 Product Information 1.2 Wide Range of Indoor 1.2 Wide Range of Indoor 1.3 Compact & Low Height Profile 1.3 Compact & Low Height Profile 1.4 Less Vibration Design 1.4 Less Vibration Design 1.5 Zero ODP Refrigerant 1.5 Zero ODP Refrigerant 1.6 Part Loading Capability 1.6 Part Loading Capability – – Tandem Type Tandem Type 1.7 Centralize Control & Networking 1.7 Centralize Control & Networking
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
R410A Water Source Split
1.1 Product Introduction 1.1 Product Introduction
- Heat pump Only
Heat pump Only
- Split Type
Split Type
- Capacity: 2.37kW
Capacity: 2.37kW – – 15.77kW 15.77kW
- 8,100 Btu/hr to 53,800 Btu/hr
8,100 Btu/hr to 53,800 Btu/hr
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
5WSS 07/ 10/ 15/ 16/ 20/ 25/ 30/ 40/ 50/ 60 AR 5WSS 07/ 10/ 15/ 16/ 20/ 25/ 30/ 40/ 50/ 60 AR 5WSS 07/ 10/ 15/ 16/ 20/ 25/ 30/ 40/ 50/ 60 AR
10 10 20 20 30 30 40 40 50 50 60 60 Btu/hr x 103 Btu/hr x 103 2.93 2.93 5.86 5.86 8.79 8.79 14.65 14.65 17.59 17.59 11.72 11.72 kW kW
Product Name Product Name
R410A Water Source Split
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
1.2 Wide Range of Indoor Option 1.2 Wide Range of Indoor Option
- 1. Features
- 1. Features
- Wall Mounted
Wall Mounted : 1 hp to 2.5 hp : 1 hp to 2.5 hp
- Ceiling Cassette
Ceiling Cassette -
- A
A : 2 hp to 5 hp : 2 hp to 5 hp
- Ceiling Cassette
Ceiling Cassette -
- C
C : 1 hp to 2 hp : 1 hp to 2 hp
- Ceiling Concealed
Ceiling Concealed : 1 hp to 6 hp : 1 hp to 6 hp
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
1.3 Compact & Low Height Profile 1.3 Compact & Low Height Profile
- 1. Features
- 1. Features
~ 30% volume metric reduction
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
1.4 Less Vibration Design 1.4 Less Vibration Design
- 1. Features
- 1. Features
- Double isolation Panel
Double isolation Panel
- Reduce noise and vibration transmission
Reduce noise and vibration transmission
Upper Panel Lower Panel Compressor Grommet
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
1.5 Zero ODP Refrigerant 1.5 Zero ODP Refrigerant
- 1. Features
- 1. Features
- In line with Montreal Protocol.
In line with Montreal Protocol.
1.6 Part Loading Capability 1.6 Part Loading Capability
- Compared to 5WSS series, 5WST series is having the part
Compared to 5WSS series, 5WST series is having the part loading capability during the low load condition, which loading capability during the low load condition, which resulting in good SEER, Seasonal EER. resulting in good SEER, Seasonal EER.
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
1.7 Centralize Control by Using NIMPC or 1.7 Centralize Control by Using NIMPC or Smart Manager/ Smart Manager/ HydroIntel HydroIntel
- 1. Features
- 1. Features
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
2.1 Handset 2.1 Handset
- 2. Handset & PCB
- 2. Handset & PCB
WM WM : G11/G12 : G11/G12 CK CK : G7/G8 : G7/G8 CC CC : SLM3 : SLM3
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- 3. Control Algorithm
- 3. Control Algorithm
3.1 System & Mode Selection 3.1 System & Mode Selection 3.2 Features 3.2 Features 3.3 Operating Mode 3.3 Operating Mode 3.4 Protection 3.4 Protection
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Modes can be selected via the value of resistor RFAN through sli Modes can be selected via the value of resistor RFAN through slide de switch. switch.
- 3. Control Algorithm
- 3. Control Algorithm
3.1 System Selection 3.1 System Selection – – 5WMWS 5WMWS
7K5 DX 22K Single 110K Multi split
ROPT2 System
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
Modes can be selected via the value of resistor RMODE Modes can be selected via the value of resistor RMODE
3.1 MODE Selection 3.1 MODE Selection – – 5WMWS 5WMWS
110K
- Cool > Dry > Fan >
EC 22K
- Auto > Cool > Dry > Fan > Heat >
AT 7K5 C2.3 version Auto > Cool > Dry > Fan > Heat > AP 3K C2.4 version Auto > Cool > Dry > Fan > Heat > AP
RMODE Defrost Modes Models
- 3. Control Algorithm
- 3. Control Algorithm
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- 3. Control Algorithm
- 3. Control Algorithm
Modes can be selected via the value of resistor ROPT2 Modes can be selected via the value of resistor ROPT2
3.1 System Selection 3.1 System Selection – – 5CCWS & 5CKWS 5CCWS & 5CKWS
Open DX 7K5 Single Shorted Tandem
ROPT2 System
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- 3. Control Algorithm
- 3. Control Algorithm
Modes can be selected via the value of resistor RMODE Modes can be selected via the value of resistor RMODE
3.1 MODE Selection 3.1 MODE Selection – – 5CCWS, 5CKWS 5CCWS, 5CKWS
110K
- Cool > Dry > Fan >
EC 22K
- Auto > Cool > Dry > Fan > Heat >
AT 7K5 C2.3 version Auto > Cool > Dry > Fan > Heat > AP 3K C2.4 version Auto > Cool > Dry > Fan > Heat > AP
RMODE Defrost Modes Models
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.2.1 Auto Random Restart 3.2.1 Auto Random Restart
- Auto random restart at the last state memory setting
Auto random restart at the last state memory setting
- Shorted at
Shorted at J_LST J_LST jumper at main board jumper at main board
- Remove the jumper to have non
Remove the jumper to have non-
- auto restart
auto restart
3.2 Features 3.2 Features
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
J_LST J_LST Auto Random Restart Auto Random Restart
3.2 Features 3.2 Features
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
Power Up Settings Power Up Settings
Power Up Power Up J_LST Shorted J_LST Shorted J_LST Opened J_LST Opened
User Set Mode User Set Mode User Set Temperature User Set Temperature User Set Fan Speed User Set Fan Speed Mode = COOL Mode = COOL Set Temperature = 24˚C Set Temperature = 24˚C Fan Speed = HIGH Fan Speed = HIGH
3.2 Features 3.2 Features
SWING OFF SWING OFF
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.2.2 Unit ON / OFF 3.2.2 Unit ON / OFF
3 ways to turn on / off the system: 3 ways to turn on / off the system: (a) On/Off Triggering (a) On/Off Triggering
- Emergency On/Off Button
Emergency On/Off Button
- System mode setting will rotate in the following
System mode setting will rotate in the following sequence sequence Heat pump Heat pump …… …….>COOL>HEAT>OFF> .>COOL>HEAT>OFF>… ….. .. Cooling Cooling …… …….>COOL>OFF> .>COOL>OFF>…… ……. .
- On/Off button on handsets
On/Off button on handsets
3.2 Features 3.2 Features
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.2 Features
3.2.2 Unit ON / OFF 3.2.2 Unit ON / OFF
(b) Delay timer (b) Delay timer
- Pressing the On/Off will reset the timer to 0 hour
Pressing the On/Off will reset the timer to 0 hour (c) Real time On/Off Timer (c) Real time On/Off Timer
- Based on internal real time clock
Based on internal real time clock
- The timer settings are kept so that similar switches can
The timer settings are kept so that similar switches can
- ccur 24 hours later.
- ccur 24 hours later.
- If emergency ON/OFF switch being press, then the timer
If emergency ON/OFF switch being press, then the timer will be reset. will be reset.
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.2 Features
3.2.3 Sleep Function 3.2.3 Sleep Function
- Only available for COOL, HEAT & AUTO mode
Only available for COOL, HEAT & AUTO mode
- This function will increase (cooling mode) or decrease
This function will increase (cooling mode) or decrease (Heating mode) the set temperature with time (Heating mode) the set temperature with time
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.2.3 Sleep Function (Cool Mode) 3.2.3 Sleep Function (Cool Mode)
SLEEP set on SLEEP set on SLEEP set off SLEEP set off
Ts Ts Ts + 1/2 Ts + 1/2 Ts + 1 Ts + 1 Ts + 2 Ts + 2 0 1/2 1/2 1 1 2 2
Hours Hours
3.2 Features
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.2 Features
SLEEP set on SLEEP set on SLEEP set off SLEEP set off
Ts Ts Ts Ts -
- 3
3 Ts Ts -
- 2
2 Ts Ts -
- 1
1 0 1/2 1/2 1 1 2 2
Hours Hours
3.2.3 Sleep Function (Heat Mode) 3.2.3 Sleep Function (Heat Mode)
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- Indoor fan speeds are
Indoor fan speeds are LOW, MEDIUM, HIGH LOW, MEDIUM, HIGH or
- r AUTO FAN
AUTO FAN in in COOL, HEAT COOL, HEAT and and AUTO AUTO modes. modes.
- In
In FAN mode FAN mode, only , only HIGH, MEDIUM HIGH, MEDIUM and and LOW LOW speeds are allowed. speeds are allowed.
3.2 Features
3.2.4 Indoor Fan Control 3.2.4 Indoor Fan Control
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- The IONIZER can be
turned ON when indoor fan is ON.
- The IONIZER will OFF
when indoor fan is OFF.
3.2 Features
3.2.5 IONIZER Control 3.2.5 IONIZER Control
Ionizer Ionizer Capacitor Capacitor
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- Available in COOL, HEAT and DRY modes only.
- When TURBO function is set, indoor fan will force to HIGH for
20 minutes and working temperature for
- Cooling Cycle is Ts – 2˚C
- Heating Cycle is Ts + 2˚C
3.2 Features
3.2.6 TURBO Function 3.2.6 TURBO Function
- If TURBO & Sleep function activated, Sleep function timer will
reset until TURBO function is clear.
Set Temperature 20min 30min TURBO Function Conventional Time
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.3. Operating Mode 3.3. Operating Mode
3.3.1 Cool Mode 3.3.1 Cool Mode 3.3.2 Heat Mode 3.3.2 Heat Mode 3.3.3 Auto Fan 3.3.3 Auto Fan 3.3.4 AUTO Mode 3.3.4 AUTO Mode 3.3.5 Defrost Function 3.3.5 Defrost Function 3.3.6 Dry Mode 3.3.6 Dry Mode
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- Compressor will cut in if Tr – Ts > 0.5˚C
- Compressor will cut out if Tr < Ts – 1.0˚C
Note: Tr = Room Temperature Ts = Set Temperature
3.3 Operating Modes
3.3.1 Cool Mode 3.3.1 Cool Mode
24°C 25°C 26°C 22°C 23°C 24.5°C 23°C
ON OFF
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.3.2 Heat Mode 3.3.2 Heat Mode
3.3 Operating Modes
- Compressor will cut in if Tr – Ts < 1.0˚C
- Compressor will cut out if Tr –Ts > 3.5˚C
Note: Tr = Room Temperature Ts = Set Temperature
3.3.2.1 Heat Pump Model 3.3.2.1 Heat Pump Model
24°C 25°C 26°C 22°C 23°C 27.5°C 23°C
OFF ON
27°C
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- The indoor fan speed modulate according to the Tin coil:
- If Tin coil > 40˚C, indoor fan run at user set speed
- If Tin coil < 18˚C, indoor fan stop
- If Tin coil crosses 30˚C, indoor fan change to low speed
Note : T Note : Tin coil
in coil = Indoor Coil Temperature
= Indoor Coil Temperature
3.3 Operating Modes
3.3.2 Heat Mode 3.3.2 Heat Mode
3.3.2.2 Hot Start 3.3.2.2 Hot Start
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- 2 selection available at the slide switch
2 selection available at the slide switch – – ON/OFF ON/OFF
- Factory Preset at
Factory Preset at OFF OFF option
- ption
3.3 Operating Modes 3.3 Operating Modes
3.3.2 Heat Mode 3.3.2 Heat Mode
3.3.2.3 Hot Keep 3.3.2.3 Hot Keep
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump When compressor cuts out, the indoor fan will runs according When compressor cuts out, the indoor fan will runs according to hot keep options. to hot keep options. There are 2 options of Hot Keep: There are 2 options of Hot Keep: (a) Fan On Option (a) Fan On Option (b) Fan Off Option (b) Fan Off Option
3.3 Operating Modes
3.3.2 Heat Mode 3.3.2 Heat Mode
3.3.2.3 Hot Keep 3.3.2.3 Hot Keep
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump (a) Fan On Option (a) Fan On Option
- Thermostat Cycle Cut OFF
Thermostat Cycle Cut OFF
- If T
If Tin coil
in coil > 40
> 40˚ ˚C, indoor fan run at set speed C, indoor fan run at set speed
- If T
If Tin coil
in coil crosses 37
crosses 37˚ ˚C, indoor fan run at low speed C, indoor fan run at low speed
- If T
If Tin coil
in coil < 18
< 18˚ ˚C, indoor fan stop C, indoor fan stop
3.3 Operating Modes
3.3.2 Heat Mode 3.3.2 Heat Mode
3.3.2.3 Hot Keep 3.3.2.3 Hot Keep
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump (b) Fan Off Option (b) Fan Off Option
- If T
If Tin coil
in coil > 40
> 40˚ ˚C, indoor fan run at set speed C, indoor fan run at set speed
- If T
If Tin coil
in coil crosses 37
crosses 37˚ ˚C, indoor fan run at low speed C, indoor fan run at low speed
- If T
If Tin coil
in coil < 30
< 30˚ ˚C, indoor fan stop C, indoor fan stop
3.3 Operating Modes 3.3 Operating Modes
3.3.2 Heat Mode 3.3.2 Heat Mode
3.3.2.3 Hot Keep 3.3.2.3 Hot Keep
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- To run heat mode, 4
To run heat mode, 4-
- way valve MUST turn ON.
way valve MUST turn ON.
- 4
4-
- way valve can only be changed from ON to OFF or vice
way valve can only be changed from ON to OFF or vice-
- versa
versa 55 +/ 55 +/-
- 5 seconds after the compressor has cut out.
5 seconds after the compressor has cut out.
- Compressor cut in after 4s.
Compressor cut in after 4s.
3.3 Operating Modes 3.3 Operating Modes
3.3.2 Heat Mode 3.3.2 Heat Mode
3.3.2.4 4 3.3.2.4 4-
- Way valve Changing
Way valve Changing
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- Cool Mode
Cool Mode
3.3 Operating Modes 3.3 Operating Modes
3.3.3 Auto Fan 3.3.3 Auto Fan
AUTO Fan Speed during COOL mode AUTO Fan Speed during COOL mode
H M L M H M L L M H M L M H M L L M H H
COMP ON COMP OFF COMP O COMP ON COMP OFF COMP ON N
+1.5 +1.5 +1.0 +1.0 +0.5 +0.5 T Ts
s
- 0.5
0.5
- 1.0
1.0
- C
C T Tr
r
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- Heat Mode
Heat Mode
3.3 Operating Modes 3.3 Operating Modes
3.3.3 Auto Fan 3.3.3 Auto Fan
T Tr
r
AUTO Fan Speed during HEAT mode AUTO Fan Speed during HEAT mode
M H M L M H M L M H M L M H M L +3.5 +3.5 +3.0 +3.0 +2.0 +2.0 +1.0 +1.0 T Ts
s
- C
C
COMP COMP OFF OFF COMP ON COMP ON COMP COMP OFF OFF
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Under Auto mode, COOL & HEAT mode can be changed Under Auto mode, COOL & HEAT mode can be changed automatically depending on room & set temperature. automatically depending on room & set temperature.
3.3 Operating Modes 3.3 Operating Modes
3.3.4 AUTO Mode 3.3.4 AUTO Mode
COOL COOL HEAT HEAT I) I) T Tr
r <= T
<= Ts
s -
- 3.5
3.5° °C AND C AND II) II) The compressor has cut out for at least 10 min The compressor has cut out for at least 10 min. .
IF IF
(a) If the present Auto mode is COOL, (a) If the present Auto mode is COOL, ( M ( Mode Set Temperature = User Set Temperature)
- de Set Temperature = User Set Temperature)
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.3.4 AUTO Mode 3.3.4 AUTO Mode
(b) If the present Auto mode is HEAT, (b) If the present Auto mode is HEAT, ( M ( Mode Set Temperature = User Set Temperature)
- de Set Temperature = User Set Temperature)
HEAT HEAT COOL COOL
IF IF
I) I) T Tr
r > T
> Ts
s + 3
+ 3° °C AND C AND II) II) The compressor has cut out for at least 10 min The compressor has cut out for at least 10 min. .
3.3 Operating Modes 3.3 Operating Modes
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.3.5 Defrost Mode 3.3.5 Defrost Mode
- Can only be operate through HEAT mode
Can only be operate through HEAT mode
- ‘
‘Defrost Timer Defrost Timer’ ’ start counting when the OD coil sensor measured start counting when the OD coil sensor measured below +3 below +3 o
- C
C
- Upon crossing + 5
Upon crossing + 5 o
- C
C to a higher temperature for 150 seconds, to a higher temperature for 150 seconds, the timer will be reset (this timer is also reset after defro the timer will be reset (this timer is also reset after defrost mode) st mode)
- The temperature sensing can only be done when the compressor
The temperature sensing can only be done when the compressor run time > 2 minutes run time > 2 minutes
3.3 Operating Modes 3.3 Operating Modes
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.3.5 Defrost Mode 3.3.5 Defrost Mode
The likelihood of ice frosting: The likelihood of ice frosting:
1/2 1 2
Hours
- C
C
+3 +2
- 2
- 4
- 6
- 8
Defrost Mode trigger if Defrost Mode trigger if >3 min >3 min
To To
3.3 Operating Modes 3.3 Operating Modes
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.3.5 Defrost Mode 3.3.5 Defrost Mode
- During Defrost Cycle, HEAT LED will blink
During Defrost Cycle, HEAT LED will blink
- The defrost cycle will terminate if:
The defrost cycle will terminate if:
- a. temperature of outdoor coil sensor exceeds
- a. temperature of outdoor coil sensor exceeds +10
+10 o
- C
C OR OR
- b. a minimum of
- b. a minimum of 10 min
10 min compressor run time is achieved compressor run time is achieved
3.3 Operating Modes 3.3 Operating Modes
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.3.5 Defrost Mode 3.3.5 Defrost Mode
OD fan OD fan & 4WV & 4WV ON ON OFF OFF ON ON OFF OFF COMP COMP
Defrost Cycle Defrost Cycle 15 +/ 15 +/-
- 5 sec
5 sec
Defrost Cycle Defrost Cycle
3.3 Operating Modes 3.3 Operating Modes
20 sec 20 sec
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.3.6 Dry Mode 3.3.6 Dry Mode
During the 1 During the 1st
st 12 minutes
12 minutes
- Run under COOL mode with Auto Fan Speed for 12 minutes
Run under COOL mode with Auto Fan Speed for 12 minutes OR OR
- Run Until
Run Until T Tr
r < T
< Ts
s –
– 1 1° °C C After the 1 After the 1st
st 12 minutes
12 minutes
- Run either Zone A, B, C or D (depend on temp. condition)
Run either Zone A, B, C or D (depend on temp. condition)
3.3 Operating Modes 3.3 Operating Modes
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.3.6 Dry Mode 3.3.6 Dry Mode
ZONE A ZONE A : if : if T Tr
r -
- T
Ts
s > 2
> 2 o
- C
C
12 Minutes 12 Minutes
3.3 Operating Modes 3.3 Operating Modes
Compressor Compressor Low Fan Low Fan ON ON OFF OFF ON ON OFF OFF
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.3.6 Dry Mode 3.3.6 Dry Mode
ZONE B ZONE B : : if 0 if 0° °C < T C < Tr
r -
- T
Ts
s < 1
< 1° °C C
8 min 8 min 4 min 4 min 30 sec 30 sec 30 sec 30 sec
ON ON OFF OFF ON ON OFF OFF 12 Minutes 12 Minutes
3.3 Operating Modes 3.3 Operating Modes
Compressor Compressor Low Fan Low Fan
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.3.6 Dry Mode 3.3.6 Dry Mode
ZONE C ZONE C : : if 1 if 1° °C < T C < Ts
s -
- T
Tr
r < 2
< 2° °C C
30 sec 30 sec 30 sec 30 sec
12 Minutes 12 Minutes
6 min 6 min 6 min 6 min
3.3 Operating Modes 3.3 Operating Modes
ON ON OFF OFF ON ON OFF OFF Compressor Compressor Low Fan Low Fan
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.3.6 Dry Mode 3.3.6 Dry Mode
ZONE D ZONE D : : if if T Ts
s -
- T
Tr
r > 3
> 3° °C C
Low Fan Low Fan Compressor Compressor
30 sec 30 sec
12 Minutes 12 Minutes ON ON OFF OFF ON ON OFF OFF
3.3 Operating Modes 3.3 Operating Modes
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.4 Protections 3.4 Protections
3.4.1 Compressor 3.4.1 Compressor 3.4.2 Indoor Coil Anti Freeze 3.4.2 Indoor Coil Anti Freeze 3.4.3 EWT Control 3.4.3 EWT Control 3.4.4 Self Diagnostics 3.4.4 Self Diagnostics
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.4 Protections
3.4.1 Compressor 3.4.1 Compressor
(a) 3 minutes Minimum OFF time (a) 3 minutes Minimum OFF time Memory backup option not selected Memory backup option not selected (J_LST Opened) (J_LST Opened)
- Compressor can immediately cut in after the power supply is
Compressor can immediately cut in after the power supply is restore; subject to thermostat cut in mode. restore; subject to thermostat cut in mode. Memory backup option selected Memory backup option selected (J_LST Shorted) (J_LST Shorted)
- Compressor can cut in 0 to 64 seconds after the power supply
Compressor can cut in 0 to 64 seconds after the power supply is restore; subject to thermostat cut in mode. is restore; subject to thermostat cut in mode.
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.4 Protections
3.4.1 Compressor 3.4.1 Compressor
(b) 150 seconds Minimum Run Time (b) 150 seconds Minimum Run Time (c) Overload Protection (c) Overload Protection COOL, AUTO COOL and DRY COOL, AUTO COOL and DRY
OD coil temp OD coil temp
Comp & OD Fan Comp & OD Fan 68 68 o
- C
C ON ON OFF OFF HEAT, AUTO HEAT HEAT, AUTO HEAT
ID coil temp ID coil temp
Comp, OD Fan Comp, OD Fan & 4WV & 4WV 68 68 o
- C
C ON ON OFF OFF
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump (d) Hardware Switch Detection (d) Hardware Switch Detection
- Normally closed switch
Normally closed switch
- A counter is increased by one during the first thermostat
A counter is increased by one during the first thermostat cycle cycle
- Counter will reset after 3 minutes or unit turned off
Counter will reset after 3 minutes or unit turned off
- If counter > 5, the unit will declare compressor overload
If counter > 5, the unit will declare compressor overload protection protection
3.4 Protections 3.4 Protections
3.4.1 Compressor 3.4.1 Compressor
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.4 Protections
3.4.2 Indoor Coil Anti Freeze 3.4.2 Indoor Coil Anti Freeze
Available in COOL and DRY mode Available in COOL and DRY mode
- IF
IF ID Coil Temp reaches 1 ID Coil Temp reaches 1° °C and below for at least 1 min C and below for at least 1 min AND AND compressor has run for at least 10 minutes compressor has run for at least 10 minutes 1 1o
- C
C Comp & OD Fan Comp & OD Fan OFF OFF ON ON 10 10o
- C
C Comp & OD Fan Comp & OD Fan OFF OFF ON ON
- IF
IF ID Coil Temp reached 10 ID Coil Temp reached 10˚ ˚C and above for at least 1 min C and above for at least 1 min
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.4 Protections
Under COOL, DRY or Auto COOL Modes, Under COOL, DRY or Auto COOL Modes,
- Compressor will NOT run and alarm will be activated
Compressor will NOT run and alarm will be activated
- IF
IF T Tw
w ≤
≤ 13 13° °C or C or T Tw
w ≥
≥ 40 40° °C for at least 20 seconds C for at least 20 seconds
- Compressor will shut down and alarm will be activated
Compressor will shut down and alarm will be activated
- IF compressor has been running for 20 seconds and
IF compressor has been running for 20 seconds and T Tw
w > 47
> 47° °C for 20 seconds C for 20 seconds
- Compressor will run and alarm will be deactivated
Compressor will run and alarm will be deactivated
- IF 13
IF 13° °C C ≤ ≤ T Tw
w ≤
≤ 40 40° °C C
3.4.3 Water Temperature Control 3.4.3 Water Temperature Control
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
Under HEAT or Auto HEAT Modes, Under HEAT or Auto HEAT Modes,
- Compressor will NOT run and alarm will be activated
Compressor will NOT run and alarm will be activated
- IF
IF T Tw
w ≤
≤ 10 10° °C or C or T Tw
w ≥
≥ 35 35° °C for at least 20 seconds C for at least 20 seconds
- Compressor will shut down and alarm will be activated
Compressor will shut down and alarm will be activated
- IF compressor has been running for 20 seconds and
IF compressor has been running for 20 seconds and T Tw
w < 6
< 6° °C for 20 seconds C for 20 seconds
- Compressor will run and alarm will be deactivated
Compressor will run and alarm will be deactivated
- IF 10
IF 10° °C C ≤ ≤ T Tw
w ≤
≤ 35 35° °C C
3.4 Protections
3.4.3 Water Temperature Control 3.4.3 Water Temperature Control
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
3.4 Protections 3.4 Protections
3.4.4 Self Diagnostics 3.4.4 Self Diagnostics
Blink E9 Blink Cool & Sleep Blink 5 times Outdoor water fault 10 Blink E8 Blink Heat, Cool, follow by Fan, Dry Blink 6 times Hardware error (tact switch pin short) 9 Blink E7 Blink Cool & Heat Blink 5 times Outdoor coil sensor exist (MS model) 8 Blink Heat Outdoor defrost 7 Blink E6 Blink Cool & Fan Blink 2 times Water pump fault 6 Blink E5 Blink Cool & Dry Blink 3 times Gas leak 5 Blink E4 Blink Cool Blink 1 time Compressor overload/ Indoor coil sensor short/ Outdoor coil/water sensor short 4 Blink E3 Blink Dry
- Blink 3 times
Outdoor coil/water sensor open 3 Blink E2 Blink Sleep
- Blink 2 times
Indoor coil sensor open 2 Blink E1 Blink Fan
- Blink 1 time
Room sensor open or short 1 Error code Error code Other Other LEDs LEDs Timer LED Timer LED CDF LED CDF LED Event Event
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- 4. Installation
- 4. Installation
4.1 Hanging the Unit 4.1 Hanging the Unit 4.2 Location of Hanging 4.2 Location of Hanging 4.3 Refrigerant Piping 4.3 Refrigerant Piping 4.4 Water Piping 4.4 Water Piping 4.5 Drainage 4.5 Drainage 4.6 Cleaning & Flushing System 4.6 Cleaning & Flushing System
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- 4. Installation
4.1 Hanging the Unit 4.1 Hanging the Unit
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- 4. Installation
4.1 Hanging the Unit 4.1 Hanging the Unit
- Recommend to use vibration isolators on
Recommend to use vibration isolators on the brackets to reduce noise and vibration the brackets to reduce noise and vibration transmissions transmissions
- Spring isolator to be used for better vibration
Spring isolator to be used for better vibration control. control.
spring bottom washer PVC tube Upper washer, welded onto bracket nut bracket
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- 4. Installation
4.2 Location of hanging 4.2 Location of hanging
Install at a location that gives sufficient space clearance for: Install at a location that gives sufficient space clearance for:
- Hanging the unit
Hanging the unit
- Installing and maintaining the water piping
Installing and maintaining the water piping
- Installing and maintaining the duct work
Installing and maintaining the duct work
- Accessing the unit
Accessing the unit’ ’s internal parts via access panel s internal parts via access panel
- Removal of air filter for cleaning
Removal of air filter for cleaning
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- 4. Installation
4.2 Location of hanging 4.2 Location of hanging
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- 4. Installation
4.3 Refrigerant Piping 4.3 Refrigerant Piping
Refrigerant Piping Length, Elevation and Bends Refrigerant Piping Length, Elevation and Bends
- When piping length becomes too long, both the capacity
When piping length becomes too long, both the capacity and compressor reliability drop. and compressor reliability drop.
- As the number of bends increases, system piping
As the number of bends increases, system piping resistance to the refrigerant flow increase thus lowering the resistance to the refrigerant flow increase thus lowering the capacity of the unit and as a result the compressor may capacity of the unit and as a result the compressor may become defective. become defective.
- Always choose the shortest path and follow the
Always choose the shortest path and follow the recommendation as tabulated in the following pages. recommendation as tabulated in the following pages.
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- 4. Installation
4.3 Refrigerant Piping 4.3 Refrigerant Piping
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- 4. Installation
4.3 Refrigerant Piping 4.3 Refrigerant Piping
Additional Charges Additional Charges
- The
The precharged precharged in the WSS unit is suitable for Standard in the WSS unit is suitable for Standard pipe of length up to: pipe of length up to:
- 2 meter for WSS10/15/20/25/30/40/50 A
2 meter for WSS10/15/20/25/30/40/50 A
- 5 meter for WSS60A
5 meter for WSS60A
- When the piping is more than the standard pipe length,
When the piping is more than the standard pipe length, additional of 18.5 gram is needed for a meter of additional additional of 18.5 gram is needed for a meter of additional length. length.
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- 4. Installation
4.4 Water Piping 4.4 Water Piping
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- 4. Installation
4.4 Water Piping 4.4 Water Piping
MODEL WATER CONNECTION IN & OUT (INCH) 5WSS10-25 AR 1/2 5WSS30-60 AR 3/4
- Males couplings, BSP
Males couplings, BSP
- In general, no pipe insulation required
In general, no pipe insulation required
Water IN Water OUT
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- 4. Installation
4.4 Water Piping 4.4 Water Piping
Flexible hose Flexible hose
- To ease water pipe installation
To ease water pipe installation
- Steel reinforced PVC hose with 2 female BSP couplings at
Steel reinforced PVC hose with 2 female BSP couplings at the end. the end.
- Use O
Use O-
- rings provided to have a leak
rings provided to have a leak-
- proof joint
proof joint
Female couplings
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- 4. Installation
4.4 Water Piping 4.4 Water Piping
Pressure gauge Water I nlet Water Outlet Gate Valve Strainer Automatic Shut-off Valve Flexible joint Thermometer Balancing Valve WSS Unit
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- 4. Installation
4.5 Drainage 4.5 Drainage
- Slanting drain pan design
Slanting drain pan design
Drain
- Drain pipe must be inclined at an angle to allow free drainage
Drain pipe must be inclined at an angle to allow free drainage
Drain pipe, ¾”
Slope downwards to the nearest drain (recommended 1:100)
U-Trap
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump
- Water circulating system must be cleaned and flushed of all
Water circulating system must be cleaned and flushed of all construction dirt and debris construction dirt and debris
- The system should be filled at the city water makeup
The system should be filled at the city water makeup connection with all air vents open. After filling, vents should connection with all air vents open. After filling, vents should be closed be closed
- Supplemental heater and circulator pump should be shut off
Supplemental heater and circulator pump should be shut off
- Use 27
Use 27° °C water as flush linger C water as flush linger
- Refill the system with clean water
Refill the system with clean water
- 4. Installation
4.6 Cleaning and Flushing System 4.6 Cleaning and Flushing System
Technical Training Technical Training Technical Training Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump Horizontal Water Source Heat Pump