18 TH INTERNATIONAL CONFERENCE ON COMPOSITE MATERIALS POLYMER MATRIX COMPOSITES IN HIGH VOLTAGE TRANSMISSION LINE APPLICATIONS M. Kumosa*, D. Armentrout, B. Burks, J. Hoffman, L. Kumosa, J. Middleton, P. Predecki Mechanical and Materials


  1. 18 TH INTERNATIONAL CONFERENCE ON COMPOSITE MATERIALS POLYMER MATRIX COMPOSITES IN HIGH VOLTAGE TRANSMISSION LINE APPLICATIONS M. Kumosa*, D. Armentrout, B. Burks, J. Hoffman, L. Kumosa, J. Middleton, P. Predecki Mechanical and Materials Engineering Department, University of Denver, Denver, USA, * Corresponding author (mkumosa@du.edu) Keywords : PMC, composite insulators, conductors, degradation, high voltage transmission 1 Background Information General Electric in the 50s. Then, over the years, the Polymer matrix composites (PMC) can be technology has been developed predominantly in highly desirable materials for various types of Europe and in the US into the second and third electrical and mechanical applications because of generation of insulators supporting, in some cases, their excellent specific properties. However, these the most critical transmission lines in many places of properties can be seriously compromised if the the world. Despite the fact that this technology has composites are subjected to extreme environments. been dramatically improved, the insulators have Many extreme environments can be envisioned, been sporadically failing in service, dropping including high voltage (HV) transmission line energized transmission lines and causing line applications (Fig. 1). outages at various utilities. Fig.1. High voltage transmission lines. Fig. 2. Non-Ceramic Insulators; (left) design and (right) in- service failure by brittle fracture of a 500kV insulator. In HV applications, Glass Reinforced Polymer (GRP) composites have been widely used The design of composite suspension in the designs of composite transmission line insulators is rather straightforward. The insulators insulators (Fig. 2), transmission and distribution rely on unidirectional GRP composite rods as the towers, and in substation applications [1-19]. principle load-bearing component (Fig. 2). The rods, However, it was been shown by Kumosa et al. [1- usually 15 mm in diameter, are manufactured by 12] that the in-service conditions can be especially pultrusion and the constituents are either polyester, damaging to the structural integrity of transmission vinyl ester, or epoxy resins reinforced with either E- line insulators based on PMC if they are improperly glass or Electric Corrosion Resistant (ECR)-glass designed. (also called boron-free E-glass) fibers. The surface Composite suspension insulators (also of the GRP rod is covered with a rubber housing referred to as either non-ceramic, polymer or material with multiple weathersheds. The purpose of polymeric insulators) are used worldwide in the housing is to protect the GRP rods against overhead transmission line applications with line outside environments (predominantly moisture, voltages in the range of 69 kV to 735 kV. The first pollution and corona discharges). composite insulator was developed in the US by

  2. The primary purpose of the weathersheds is strength core is based on continuous carbon fibers to increase the leakage distance between the embedded in a high temperature epoxy. The carbon energized and ground ends of the insulators and to core is surrounded by a thin sheath of unidirectional protect the GRP rod against the outside dielectric ECR-glass fiber/high temperature epoxy environment. Today, common housing materials are composite. The glass/epoxy layer is incorporated ethylene-propylene rubbers, different types of into the design in order to prevent a direct electrical silicon rubbers and ethylene vinyl acetate-based path between the conducting aluminum wires and elastomers. Other composite insulators such as the conductive carbon fibers, preventing a potential substation or line post insulators are based on the galvanic reaction. same design. However, they usually rely on large To mitigate stress corrosion cracking of the GRP rods, up to 50 mm in diameter. There are two glass fiber composite portion of the conductor [4], metal end fittings attached to the GRP rods at both corrosion resistant ECR (boron free) glass fibers are ends of the insulators (Fig. 2). In modern composite used. The current expectation is that the PMC insulators the fittings are usually attached to the rod conductors, especially the ACCC design, should be by crimping [2]. able to transport, in theory, up to 3 times more In spite of many benefits, which the electric current at much higher temperatures (up to insulators can offer in comparison with their 180°C) and significantly reduce sagging. These porcelain counterparts (high mechanical strength-to- advantages could revolutionize power transmission weight ratio, improved damage tolerance, flexibility, world-wide. good impact resistance, and ease of installation), In this review paper the most important they can fail mechanically in service by rod fracture, accomplishments from the composite insulator and electrically by flashover [1-12]. research performed between 1993 and 2007 [1-6,8- 12] in our laboratory and its impact on the global transmission line systems and the global economy are described. Then, our current on-going HT PMC conductor research [14-17, 19], its’ most important findings thus far, and its’ international importance is presented. 2 In-Service Stresses on PMC HV Insulators and Conductors In-service, PMC insulators and conductors Fig. 3. High Voltage PMC conductor; (left) schematic and (right) design of ACCC. are subjected to the combined action of severe mechanical, electrical and environmental (chemical) PMCs are also beginning to be used in the stresses [1-19]. The mechanical stresses consist of next generation HV high temperature (HT) electric multi-axial loads caused by the weight of the lines, conductors (Fig. 3) [13-19]. Present overhead manufacturing residual stresses, dynamic stresses electrical conductors are based on either the caused by Aeolian vibrations (high cycle fatigue) Aluminum Conductor Steel Reinforced (ACSR) or and line galloping (low cycle fatigue), complex Aluminum Conductor Steel Supported (ACSS) multi-axial stresses dominated by transverse design. These lines are subject to significant compression near the mechanical connections amounts of sag during HT operation. Thus, new (suspension clamps). In addition, the lines can be designs of HV overhead conductors have been affected by the manufacturing/installation stresses considered for potential applications [13], which created by excessive bending of the conductors could reduce the “sag problem,” and allow more around mandrels, travelers and tensioners, and power to be transmitted using the existing structures. mishandling of the insulators mostly during either One of the new designs, known as the Aluminum manufacturing or installation. The electrical and Conducting Composite Core (ACCC TM ) conductor environmental stresses imposed on the PMC [13], is based upon hybrid PMC core rods with two insulators and conductors in-service are equally different reinforcing fibers (Fig. 3). The inner high

Download Presentation
Download Policy: The content available on the website is offered to you 'AS IS' for your personal information and use only. It cannot be commercialized, licensed, or distributed on other websites without prior consent from the author. To download a presentation, simply click this link. If you encounter any difficulties during the download process, it's possible that the publisher has removed the file from their server.

Recommend


More recommend