Modelling and Dynamic Performance Analysis of the Power System Under - - PowerPoint PPT Presentation

Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response Hongxun Hui 1 , Yi Ding 1* , Yonghua Song 2,3,1 , Saifur Rahman 4 1. College of Electrical Engineering, Zhejiang


slide-1
SLIDE 1

Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

Hongxun Hui1, Yi Ding1*, Yonghua Song2,3,1, Saifur Rahman4

  • 1. College of Electrical Engineering, Zhejiang University, Hangzhou, China

2 State Key Laboratory of Internet of Things for Smart City, University of Macau, Macau, China 3 Department of Electrical and Computer Engineering, University of Macau, Macau, China 4 Advanced Research Institute, Virginia Tech, Arlington, VA, USA

August 2019

slide-2
SLIDE 2

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

Contents

Background

1.

Modelling of the power system considering demand response

2.

Stability of the power system with and without demand response

3.

Case studies

4.

Discussions and conclusions

5.

slide-3
SLIDE 3

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

  • 1. Background

[1] Wu H, et al. Administrative investigation report on the 815 power failure. Executive Yuan, Taiwan, Republic of China, Tech. Rep. 1060907,

  • Sep. 2017. <http://www.ey.gov.tw>

[2] U.S. News. Tens of Millions in Northern Brazil Hit by Massive Power Outage. <https://www.usnews.com/news/world/articles/2018-03- 21/tens-of-millions-in-northern-brazil-hit-by-massive-power-outage>

  • Fig. 1 The blackout in Taiwan on Aug. 15, 2017
  • The large-scale blackouts are increasing.

The blackout in Taiwan on Aug. 15, 2017 affected about 6.68 million customers[1]. The blackout in Brazil on Mar. 21, 2018 resulted in 22.5% failure of power output[2].

  • The fundamental reason is the shortage of the operating reserve and

frequency .

  • Fig. 2 The blackout in UK on Aug. 9, 2019
slide-4
SLIDE 4

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

  • 1. Background

[3] Rebours YG, Kirschen DS, Trotignon M, Rossignol S. A survey of frequency and voltage control ancillary services—Part I: Technical features. IEEE Trans. Power Syst., vol. 22, no. 1, pp. 350-357, Feb. 2007. [4] Siano P. Demand response and smart grids—A survey. Renew. Sustain. Energy Rev., vol. 30, pp. 461-478, Feb. 2014.

  • Fig. 3 Traditional generation units

Conventionally, the operating reserve is provided by traditional generation units, such as the thermal power plants or hydro turbines[3].

https://images.app.goo.gl/Rif nP6ZJK7cVs3Fy5

The development of the information and communication technology makes it easier for household appliances to provide

  • perating reserve, which we can

call smart home[4].

  • Fig. 4 Smart home system

https://images.app.goo.gl /BsbAS8e3F4CuP87V6

slide-5
SLIDE 5

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

  • 1. Background

[5] Hui H, Ding Y, Liu W, Lin Y, Song Y. Operating reserve evaluation of aggregated air conditioners. Appl. Energy, vol. 196,

  • pp. 218-228, Jun. 2017.

[6] Hui H, Ding Y, Zheng M. Equivalent modeling of inverter air conditioners for providing frequency regulation service. IEEE Transactions on Industrial Electronics. 2019 Feb;66(2):1413-23. [7] Xie D, Hui H, Ding Y, Lin Z. Operating reserve capacity evaluation of aggregated heterogeneous TCLs with price signals. Applied Energy. 2018 Apr 15;216:338-47. [8] Cai M, Pipattanasomporn M, Rahman S. Day-ahead building-level load forecasts using deep learning vs. traditional time- series techniques. Applied Energy. 2019 Feb 15;236:1078-88. [9] Shi Q, Li F, Liu G, Shi D, Yi Z, Wang Z. Thermostatic Load Control for System Frequency Regulation Considering Daily Demand Profile and Progressive Recovery. IEEE Transactions on Smart Grid. 2019 Feb 21. [10] Zhang X, Pipattanasomporn M, Rahman S. A self-learning algorithm for coordinated control of rooftop units in small-and medium-sized commercial buildings. Applied Energy. 2017 Nov 1;205:1034-49. [11] Pourmousavi SA, Nehrir MH. Introducing dynamic demand response in the LFC model. IEEE Transactions on Power

  • Systems. 2014 Jul;29(4):1562-72.

[4] Siano P. Demand response and smart grids—A survey. Renewable and Sustainable Energy Reviews. 2014 Feb 1;30:461- 78. [5] Shi Q, Li F, Hu Q, Wang Z. Dynamic demand control for system frequency regulation: Concept review, algorithm comparison, and future vision. Electric Power Systems Research. 2018 Jan 1;154:75-87.

  • However, most of papers only focus on the load power disturbance

scenarios.

  • The dynamic performance of the power system with DR has not

been studied under unit contingency shutdown accidents.

slide-6
SLIDE 6

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

Contents

Background

1.

Modelling of the power system considering demand response

2.

Stability of the power system with and without demand response

3.

Case studies

4.

Discussions and conclusions

5.

slide-7
SLIDE 7

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

  • 2. Modelling of the power system considering

demand response

[13]Hui H, Ding Y, Luan K, Xu D. Analysis of "815" Blackout in Taiwan and the Improvement Method of Contingency Reserve Capacity Through Direct Load Control. In2018 IEEE Power & Energy Society General Meeting (PESGM) 2018 Aug 5 (pp. 1-5). IEEE. [14]Mohanty B, Panda S, Hota PK. Controller parameters tuning of differential evolution algorithm and its application to load frequency control of multi-source power system. International Journal of Electrical Power & Energy Systems. 2014 Jan 1;54:77-85. [15]Parmar KS, Majhi S, Kothari DP. Load frequency control of a realistic power system with multi-source power generation. International Journal of Electrical Power & Energy Systems. 2012 Nov 1;42(1):426-33.

1 T

P  DSRs 1

PS PS

K sT  f 

dev D

P  

DR

P   

  

1 1 1 1

1 1 1

HP r t r

sF T sT sT   

1

1 1

g

sT 

1 T

1

1

T

R

1 T

K s  

  

1 1 1

HPn rn tn rn

sF T sT sT    1 1

gn

sT 

Tn

1

Tn

R

Tn

K s  

… …

  

1 1 1

1 1 1

CR F CD

sT sT sT   

1 1

1 1

G G

sX sY  

1 G

 

1 G

K s  

1 1

1

G G

c sb 

  

1 1 1

CRm Fm CDm

sT sT sT    1 1

Gm Gm

sX sY  

Gm

 

Gm

K s   1

Gm Gm

c sb    

1

1

G

R 1

Gm

R

   

Tn

P 

1 G

P 

Gm

P 

… … … … … … …

 Controller 

Demand Response

G

P 

Reheat steam generators Gas turbine generators

slide-8
SLIDE 8

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

  • 2. Modelling of the power system considering

demand response

1 1

( ) ( )

n m Ti Ti Gj Gj i j

G s G s  

 

 

f 

dev D

P  

DR

P 

 

 ( )

DR DR

H s 

G

P  1

PS PS

K sT 

Reheat steam generators Gas turbine generators Demand response

  

1 1 1 ( ) 1 1 1

Ti HPi ri Ti Ti gi ti ri

K sF T G s R s sT sT sT                – Power generation by reheat steam generators : – Power generation by gas turbine generators :

  

1 1 1 1 ( ) 1 1 1

Gj Gj CRj Gj Gj Gj Gj Gj Fj CDj

K sX sT G s R s c sb sY sT sT                    

(1) (2)

slide-9
SLIDE 9

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

  • 2. Modelling of the power system considering

demand response

1 1

( ) ( )

n m Ti Ti Gj Gj i j

G s G s  

 

 

f 

dev D

P  

DR

P 

 

 ( )

DR DR

H s 

G

P  1

PS PS

K sT 

Reheat steam generators Gas turbine generators Demand response

1 ( )

DR DR DR

K H s R s          – Regulation power by demand side resources :

1 ( ) ( )

DR DR DR DR DR DR

K G s H s R s            

(3.1) (3.2)

slide-10
SLIDE 10

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

Contents

Background

1.

Modelling of the power system considering demand response

2.

Stability of the power system with and without demand response

3.

Case studies

4.

Discussions and conclusions

5.

slide-11
SLIDE 11

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

  • 3. Stability of the power system with and

without demand response

1 1 ( )

( ) ( ) ( ) ( ) 1 ( ) ( ) ( ) ( )

dev n m D Ti Ti Gj Gj DR DR i j s

f s M s s P s M s G s G s H s   

  

              

 

1 1

( ) ( ) ( ) ( )

n m G Ti Ti Gj Gj i j

P s G s G s f s  

 

         

 

– The system frequency deviations:

 

( ) ( ) ( ) ( ) 1

dev PS G DR D PS

K f s P s P s P s sT        

– The closed-loop transfer function with regard to the disturbance load power:

Regulation power provided by DR (6)

(7) (4)

( ) ( ) ( )

DR DR DR

P s H s f s    

Regulation power provided by generators (5)

slide-12
SLIDE 12

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

  • 3. Stability of the power system with and

without demand response

– The power generation losses can be regarded as the disturbance power:

( ) ( ) ( )

Tk Tk Gl Gl dev D

G s G s P s s s     

– The closed- and open-loop transfer functions of the power system will get changed from (7), when the unit contingency shutdown accident occurs: (7) (9)

1 1 ( )

( ) ( ) ( ) ( ) 1 ( ) ( ) ( ) ( )

dev n m D Ti Ti Gj Gj DR DR i j s

f s M s s P s M s G s G s H s   

  

              

 

(10)

1, 1,

( ) ( ) ( ) ( ) ( )

n m Ti Ti Gj Gj DR DR i i k j j l

s M s G s G s H s   

   

         

 

slide-13
SLIDE 13

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

  • 3. Stability of the power system with and

without demand response

– The power generation losses can be regarded as the disturbance power:

Gain Margin w/o DSRs w/ 2% DSRs w/ 4% DSRs Phase Margin Both the gain margin and phase margin can be increased by DSRs. Scenarios Gain Margin Phase Margin w/o DSRs 19.4 dB (at 3.67 rad/s) 59.8 deg (at 0.807 rad/s) w/ 2% DSRs 20.3 dB (at 3.87 rad/s) 60.2 deg (at 0.821 rad/s) w/ 4% DSRs 21.4 dB (at 4.11 rad/s) 60.5 deg (at 0.835 rad/s)

Table 2 The gain and phase margins of the Bode plots.

slide-14
SLIDE 14

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

Contents

Background

1.

Modelling of the power system considering demand response

2.

Stability of the power system with and without demand response

3.

Case studies

4.

Discussions and conclusions

5.

slide-15
SLIDE 15

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

  • 4. Case Studies

The test system

  • The test system adopts the power system in Fig. 1.
  • It is assumed that one gas turbine generator is shut down suddenly,

which is similar with the actual gas generating plant accident in Taiwan.

1 T

P  DSRs 1

PS PS

K sT  f 

dev D

P  

DR

P   

  

1 1 1 1

1 1 1

HP r t r

sF T sT sT   

1

1 1

g

sT 

1 T

1

1

T

R

1 T

K s  

  

1 1 1

HPn rn tn rn

sF T sT sT    1 1

gn

sT 

Tn

1

Tn

R

Tn

K s  

… …

  

1 1 1

1 1 1

CR F CD

sT sT sT   

1 1

1 1

G G

sX sY  

1 G

 

1 G

K s  

1 1

1

G G

c sb 

  

1 1 1

CRm Fm CDm

sT sT sT    1 1

Gm Gm

sX sY  

Gm

 

Gm

K s   1

Gm Gm

c sb    

1

1

G

R 1

Gm

R

   

Tn

P 

1 G

P 

Gm

P 

… … … … … … …

 Controller 

Demand Response

G

P 

Reheat steam generators Gas turbine generators

slide-16
SLIDE 16

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

  • 4. Case Studies

The simulation results

30 60 90 120 150 180 210 240

  • 0.40
  • 0.35
  • 0.30
  • 0.25
  • 0.20
  • 0.15
  • 0.10
  • 0.05

0.00 0.05 The maximum system frequency deviation decreases with more DSRs for DR.

  • 0.1352Hz
  • 0.2023Hz

System Frequency Deviations (Hz) Time (s) f (w/o DSRs) f (w/ 2% DSRs) f (w/ 4% DSRs)

  • 0.3277Hz
  • Fig. 4 System frequency deviations in the three cases when one

gas turbine generator is shut down.

slide-17
SLIDE 17

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

  • 4. Case Studies

The simulation results

5 10 15 20 4700 4800 4900 5000 5100 Power Deviations (MW) Time (s)

PThermal (w/o DSRs) PThermal (w/ 2% DSRs) PThermal (w/ 4% DSRs)

(a) 5 10 15 20 1600 1700 1800 1900 2000 2100 Power Deviations (MW) Time (s)

PGas (w/o DSRs) PGas (w/ 2% DSRs) PGas (w/ 4% DSRs)

(b) 5 10 15 20 100 200 300 400 Power Deviations (MW) Time (s)

PDR (w/ 2% DSRs) PDR (w/ 4% DSRs)

(c)

  • Fig. 5 Power deviations in the three

cases: (a) the total power deviations of the reheat steam generators, (b) the total power deviations of the gas turbine generators, (c) the regulation power provided by DSRs.

slide-18
SLIDE 18

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

  • 4. Case Studies

The simulation results

30 60 90 120 150 180 210 240

  • 0.40
  • 0.35
  • 0.30
  • 0.25
  • 0.20
  • 0.15
  • 0.10
  • 0.05

0.00 0.05 The system frequency deviations become less when the reheat steam generator is shut down while not the gas turbine generator.

  • 0.1341Hz
  • 0.1956Hz

System Frequency Deviations (Hz) Time (s) f (w/o DSRs) f (w/ 2% DSRs) f (w/ 4% DSRs)

  • 0.3162Hz
  • Fig. 6 System frequency deviations in the three cases

when one reheat steam generator is shut down.

slide-19
SLIDE 19

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

Contents

Background

1.

Modelling of the power system considering demand response

2.

Stability of the power system with and without demand response

3.

Case studies

4.

Discussions and conclusions

5.

slide-20
SLIDE 20

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

  • 5. Discussions and Conclusions

– Faced with the increasing generating unit contingency shutdown accidents, this paper proposes an alternative method of traditional generators to provide regulation power by DSRs. – Firstly, the power system model considering DR is developed. On this basis, the transformed closed- and open-loop transfer functions are derived. – Then, the Bode plots are obtained to analyze the dynamic performances of the power system under unit contingency shutdown accidents, which illustrates that the stability of the power system can be enhanced by DR. – The numerical studies show that the maximum system frequency deviation can be decreased from -0.3277Hz to -0.1352Hz when the DR is considered. – The proposed models and methods in this paper contribute to guiding the DR in the power systems, especially in the countries and regions where reserve capacities are insufficient.

– Our future work.

slide-21
SLIDE 21

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

Demonstration——Friendly Interactive System of Supply and Demand (FISSD)

Demonstration area in Suzhou:

  • Administrative region: 78 km2
  • Resident population: 780,000

 Large industry customers:1420  Commercial customers:32437  Residential customers: 352,600

  • Load aggregators: 5

Demonstration area in Changzhou:

  • Administrative region: 182 km2
  • Resident population: 1,600,000

 Large industry customers:590  Commercial customers:21755  Residential customers: 530,000

  • Load aggregators: 3

It is approved and supported by Ministry of Science and Technology of the People’s Republic of China.(2016-2020)

slide-22
SLIDE 22

College of Electrical Engineering Zhejiang University International Conference on Applied Energy Paper (295): Modelling and Dynamic Performance Analysis of the Power System Under Unit Contingency Shutdown Accidents Considering Demand Response

Thanks for your attention!