Electrical Electrical Requirements Permit Application OVERVIEW - - PDF document

electrical
SMART_READER_LITE
LIVE PREVIEW

Electrical Electrical Requirements Permit Application OVERVIEW - - PDF document

Electrical Electrical Requirements Electrical Requirements Presented by: Mark Izzo Electrical Plan Examiner 1 C I T Y O F C H I C A G O D E P A R T M E N T O F B U I L D I N G S Electrical Electrical


slide-1
SLIDE 1

1

Electrical

C I T Y O F C H I C A G O D E P A R T M E N T O F B U I L D I N G S

Electrical Requirements

1

Electrical Requirements

Presented by:

Mark Izzo

Electrical Plan Examiner

Electrical

C I T Y O F C H I C A G O D E P A R T M E N T O F B U I L D I N G S

Electrical Requirements

2

OVERVIEW

  • Permit Application
  • Required Plans
  • Required Emergency

Systems

  • Sign Permits
  • Summary
  • Questions & Answers
slide-2
SLIDE 2

2

Electrical

C I T Y O F C H I C A G O D E P A R T M E N T O F B U I L D I N G S

Electrical Requirements

3

ELECTRICAL PERMIT APPLICATION

Electrical

C I T Y O F C H I C A G O D E P A R T M E N T O F B U I L D I N G S

Electrical Requirements

4

PREPARATION

  • Review project for any existing

code violations.

  • Review suspension file to insure

contractor is eligible to obtain permits.

  • Review any letters of special

permission.

slide-3
SLIDE 3

3

Electrical

C I T Y O F C H I C A G O D E P A R T M E N T O F B U I L D I N G S

Electrical Requirements

5

REF 18-27-215.5

Electrical plans required for:

  • Dwelling-type occupancies greater

than two stories.

  • Commercial and/or industrial-type
  • ccupancies greater than one story
  • r greater than 10,000 feet in area.
  • Warehouses greater than two

stories.

  • Service switchboards and motor

control centers rated in excess of 1,200 amperes or 600 volts.

  • New or Replacement Services of

400 Amps or greater.

Electrical

C I T Y O F C H I C A G O D E P A R T M E N T O F B U I L D I N G S

Electrical Requirements

6

REF 18-27-215.5 (continued)

  • Electrical heating systems

with connected loads in excess of 5 kw.

  • Data processing systems.
  • Swimming pools.
  • Exit and emergency lighting

systems.

  • Required fire alarm systems.
  • As directed by the Chief Electrical

Inspector.

slide-4
SLIDE 4

4

Electrical

C I T Y O F C H I C A G O D E P A R T M E N T O F B U I L D I N G S

Electrical Requirements

7

PLAN CONTENT

  • Single line drawing of the service

and distribution.

  • Schedule of conduits, wire,

switches, circuit breakers, over current devices, transformers, motors and fixtures.

  • Load calculations for service,

feeders and panel boards indicating available fault-current and withstand ratings.

Electrical

C I T Y O F C H I C A G O D E P A R T M E N T O F B U I L D I N G S

Electrical Requirements

8

PLAN CONTENT (continued)

  • Grounding detail, including

grounding electrode conductor or common grounding electrode conductor system.

  • Equipment layout in switchboard

rooms and electrical closets indicating the required workspace.

slide-5
SLIDE 5

5

Electrical

C I T Y O F C H I C A G O D E P A R T M E N T O F B U I L D I N G S

Electrical Requirements

9

PLAN CONTENT

Special Services Switchboard

  • Switchboard with a single

disconnecting means having a frame rating in excess of 1,200 amperes or a sequence service switchboard where the sum of the frame size exceeds 1,200 amperes.

  • Drawing submittal requirements.
  • Review and approval.

Electrical

C I T Y O F C H I C A G O D E P A R T M E N T O F B U I L D I N G S

Electrical Requirements

10

REQUIRED EMERGENCY SYSTEMS

  • Location of all exit and emergency lights on

scaled floor plans.

  • Review of single line drawing of emergency

service and distribution showing sizes of conduit, conductors, switches and over current devices.

  • Detail all loads and locations of emergency

lighting equipment.

  • If applicable, generators must comply with

Article 701, Section 18-27-701.6.

  • Exceptions.
slide-6
SLIDE 6

6

Electrical

C I T Y O F C H I C A G O D E P A R T M E N T O F B U I L D I N G S

Electrical Requirements

11

FIRE ALARM SYSTEM Fire Alarm and Emergency Voice Communication Systems

  • This is a separate submittal of shop

drawings by the FA contractor AFTER the building permit has been issued.

  • Two complete raceway diagrams showing

all horizontal and lateral sections and two corresponding circuit diagrams.

  • Show the circuits of the control panel,

alarm sending stations, automatic detectors, alarm sounding devices, supervisory test switches, trouble sounding device, trouble sounding device test switch, pilot light and switch.

Electrical

C I T Y O F C H I C A G O D E P A R T M E N T O F B U I L D I N G S

Electrical Requirements

12

(continued)

  • Submit two one-line wiring

diagrams showing the service entrance conductors, equipment and fire alarm supply source.

  • Full load calculations for all

initiating and signaling circuits.

  • Please refer to the handout in your

manual. EMERGENCY SYSTEMS

slide-7
SLIDE 7

7

Electrical

C I T Y O F C H I C A G O D E P A R T M E N T O F B U I L D I N G S

Electrical Requirements

13

SIGN PERMITS

A Separate Sign Permit is Required for:

  • Building mounted flat and projecting signs as

well as bill board signs, free standing signs, printed awnings and monument signs

– Includes electric and non-electric signs – Sign permit application must be submitted online by the sign contractor – Zoning review is required – Site plan and construction details required – May require structural calculations – Use of public way is required for signs located in

  • r projecting into the public way

Electrical

C I T Y O F C H I C A G O D E P A R T M E N T O F B U I L D I N G S

Electrical Requirements

14

SUMMARY

  • Make sure to complete both the

DOB Permit Application and the Electrical Application.

  • Follow the guidelines reviewed for

submitting single line drawings, load calculations, grounding detail and equipment layouts.

  • Follow the Electrical Plan

Examination Checklist to avoid mistakes.

slide-8
SLIDE 8

8

Electrical

C I T Y O F C H I C A G O D E P A R T M E N T O F B U I L D I N G S

Electrical Requirements

15

CONTACT INFORMATION

  • For Electrical questions contact:

dcapelectr@cityofchicago.org

  • For Electrical Plan Review or

Sign Permit Questions contact:

312-744-7955 312-744-3472

  • To schedule an inspection visit

www.cityofchicago.org/buildings and select “Request Inspection”

Electrical

C I T Y O F C H I C A G O D E P A R T M E N T O F B U I L D I N G S

Electrical Requirements

16

QUESTIONS & ANSWERS