resource conservationtraining 27 january 2016
play

Resource ConservationTraining 27 January 2016 Conserving Energy in - PDF document

Resource ConservationTraining 27 January 2016 Conserving Energy in Presentation Outline Compressed Air Systems How Much Does CAir Cost -Introduction Presented to the Supply Side Components how they perform and work together


  1. Resource ConservationTraining 27 January 2016 Conserving Energy in Presentation Outline Compressed Air Systems • How Much Does CAir Cost -Introduction Presented to the • Supply Side – Components – how they perform and work together MA Toxic Use Reduction Institute – Where to look for savings Resource Conservation Training • Demand Side January 27, 2016 – System components By – Appropriate and inappropriate uses – Control Issues Jim Guertin, P.E., AIRMaster+ Specialist – Where to look for savings UTS Energy Engineering 617-471-3454 jim@UTSee.com Welcome to the Wonderful World of 10 Year Compressor Compressed Air Ownership Costs CAir analysis needs a different mind set. Example: A leak is blowing out 100 CFM Questions: Will more air be wasted at 50 psi or 100 psi? Assumptions: Will more energy be wasted at 50 psi or 100 psi? 75-hp compressor, 2 shifts a day, 5 days a week over 10 years of equipment life. Typical CAir System Cost of Compressed Air Example: 6” grinder: 50 CFM or 1.0 kW electric 18 kW / 100 CFM (typical eff. of comp.) 18 kW / 100 x 50 = 9 kW 9 / 1 = CAir is 9 times more expensive With only 50% effective conversion rate CAir is 18 times more expensive (1 constant CFM > $237/year @ $0.15/kWh) 1

  2. Resource ConservationTraining 27 January 2016 Types of Compressors Supply Side Components • Compressors • Traps –Controls • Receiver • Dryers • Filters –Controls Operating Range of Compressor Types Double Acting 2 Stage Reciprocating Double Acting 2 Stage Reciprocating 2

  3. Resource ConservationTraining 27 January 2016 Small On/Off Reciprocating Reciprocating Compressor Controls • On / Off • Step Unloading Centrifugal Compressor Centrifugal Compressor Centrifugal Compressor Control • Modulating – Inlet Guide Vanes – Butterfly Valve • Dual / Auto Dual 3

  4. Resource ConservationTraining 27 January 2016 Cut Away of a Screw Screw Compressor Screw Geometry Control Screw Compressor Controls • Modulating (Inlet Valve) • Load / Unload • Dual / Auto Dual • Geometry (Turn/Spiral, Poppet valves) • Variable Speed • Effects of Receiver Size 4

  5. Resource ConservationTraining 27 January 2016 Screw Compressor Control Comparisons On-Line/Off-Line Cycle 110 100 90 80 % of Full Load BHP 70 60 Inlet Modualtion 50 Geometry 40 Online/Offline 3 gal/cfm 30 VSD 20 On / Off 10 0 0 10 20 30 40 50 60 70 80 90 100 % of Full Load CFM CAGI Compressor Data Sheet Rotary Compressor: Fixed Speed CAGI Compressor Data Sheet Air Compressor Curve Tool.XLS -- INPUTS Rotary Compressor: Variable Speed Drive 5

  6. Resource ConservationTraining 27 January 2016 Air Compressor Curve Tool.XLS Air Compressor Curve Tool.XLS OUTPUTS Compressor Control Type COMPRESSOR #1 110% 100% From TAB: Outputs - Tables 90% 80% % of Full Load KW 70% 60% 50% 40% 30% 20% 10% 0% 0% 20% 40% 60% 80% 100% % of Full Load CFM From TAB: Outputs - Curves Other Common Types of Liquid Ring Air Compressor Compressors • Liquid Ring • Sliding Vane • Axial • Lobe Sliding Vane Compressor Axial Compressor 6

  7. Resource ConservationTraining 27 January 2016 Lobe Compressor Compressor Conservation Measures • Lower operating pressure – 1% savings for each 2 psi drop • Coordinate control of multiple comps – Partly load only one compressor • Add storage for on-line/off-line controlled compressors • Get intake air from outside • Turn off during unoccupied times Refrigerated Cold Dryer Regeneration Desiccant Non-Cycling Dryer Cycling Dew points to - 90 F Dew points to 28 F Purge ~ 20% of rated 7

  8. Resource ConservationTraining 27 January 2016 Desiccant Dryers Heat Of Compression Dryer Internal heat reactivated External heat reactivated Dew points to - 40 F Dew points to - 40 F Purge ~ 5% of rated Purge ~ 2% of rated Dryer Conservation Measure Receiver Location – Before Dryer For ~ 35F dew points Advantages: • Replace non-cycling refrigerated dryer – Favorable dryer size. with cycling refrigerated dryer – Non-turbulent flow • Clean air-cooled condenser – Lower CAir entry temp. – Lower condensate For < 20F dew points amount • Install heat of compression dryer Disadvantages: • Install dew point control on desiccant – Condensate in receiver dryers – Overload of the Dryer CAGI Dryer Data Sheet Receiver Location – After Dryer Refrigerated Dryers Advantages: – No condensate in receiver – Consistent CAir quality Disadvantages: – Large size dryer – Stress with Recip. – High entry temp of CAir – Large quantity of condensate – Each compressor has its own dryer 8

  9. Resource ConservationTraining 27 January 2016 Timed Cycle Trap – Very reliable operation – Electricity connection required – No alarm function – Operates all the time no matter the CAir load – Doesn’t differentiate between air and water Air and Water Leakage.XLS Electronic Level Sensing Trap – Very reliable operation 3 even with problematic 4 condensates 1 – Large discharge – No pressure loss – Electricity connection 5 required – Alarm function – External malfunction signal. Mechanical Float Trap Trap Conservation Measure – Very reliable operation even with • Avoid manual blow down problematic • Replace Timed Cycle Trap condensates – Large discharge • Periodically check traps for proper – No pressure loss operation – Electricity connection • Periodically clean traps required – Alarm function (at 3) 9

  10. Resource ConservationTraining 27 January 2016 Filters Filter Conservation Measures Particulate • Replace with low pressure drop filters • Dust separator > 50 micron – Will only save energy if compressor operating • Pre-filter > 3 micron pressure reduced • Micro filters > 0.01 micron ( 1% kW saved for each 2 psi drop ) Coalescing • Removes particles, moisture and oil to 0.1 microns Supply Side Conservation Measures ECO Savings Low pressure drop inlet filter 2% More efficient compressor 10-15% Replace/Stop leaking isolation valve 10-20 cfm Micro processor sequencer shut off idling compressor, reduce deadband Replace condensate traps 40-80 cfm Replace filters 3-10 psi Replace dryer >50% of dryer usage Demand Side of Demand Side Components Typical Industrial CAir User Distribution System • Demand Expander / Intermediate Pressure Controller • Piping • Hoses • FLR (filter, lubricator, regulator) 10

  11. Resource ConservationTraining 27 January 2016 Demand Expander Demand Side Components • A very quick acting full bore pressure reducer End Uses Advantages • Productive uses • Reduces leakage • Inappropriate uses • Reduces artificial demand • Leakage • Adds capacitance to system • Artificial demand Disadvantage • Requires compressor to operate at higher pressures Demand Side Conservation Measures Reduce Productive Usage • Replace nozzles with engineered nozzles • Purchase more conservative equipment Demand Side Conservation Measures Inappropriate Uses of CAir See Handout: Potentially Inappropriate Uses of Compressed Air 11

  12. Resource ConservationTraining 27 January 2016 Demand Side Conservation Measures Reduce Artificial Demand • Demand Expander / Pressure Controller • Remote Storage • End Use Pressure Regulators • Reduce System Pressure • Loop Header • Enlarge Piping • Low Pressure Drop Filters and other components Demand Side Conservation Measures Testing For Leakage • Ultrasonic leak detector • Receiver bleed down test Volume * ( P1 - P2) Leakage, CFM = * 1.25 Time * 14.7 P1 = start pressure, psig P2 = end pressure, psig Volume is in cubic feet Time is in minutes If leakage is > than 10% of compressor capacity action should be taken Reduce Leakage Heat Recovery • Perform Detailed Survey • Make Leak Repairs • Institute On Going Leak Reduction Program 12

  13. Resource ConservationTraining 27 January 2016 Available Heat To Recover Demand Side Conservation Measures Compressor Heat Calculator.XLS ECO Savings Demand Expander / Pressure regulator 10 - 15 psi Leaks, quick disconnects, open nozzles 10% or more Point of use storage 5 - 10 psi Complete loop 2.5 - 5 psi New main 3 - 8 psi New drops 2 - 6 psi Rules Of Thumb Rules Of Thumb • Air compressors normally deliver 4 to 5 cfm per horsepower at 100 psi • Total pressure drop across all components should not be • Every 2 psi pressure change in pressure equals 1% greater than 15 psi change in compressor power draw • Locate filters and dryers in the air line before any pressure reducing valve (highest pressure) and after air • Power cost for each hp operating constantly for 1 year = is cooled to 100ºF or less (lowest temperature) $1,100 @ 15¢/kwh • Water cooled after coolers require ~ 3 gpm per 100 cfm • A 50 hp compressor rejects heat at about 126,000 btu/h @100 psig and about 119,000 (> 90%) is recoverable • Most air motors require 30 cfm at 90 psig per • Water vapor content of 100ºF saturated compressed air horsepower rating = ~ 2 gallons per hour per 100 cfm • At 100 psig every 20ºF increase in saturated air temp • Every 100 cfm of 100 psig air produces 20 gallons of DOUBLES the amount of moisture in the air condensate per day 13

Download Presentation
Download Policy: The content available on the website is offered to you 'AS IS' for your personal information and use only. It cannot be commercialized, licensed, or distributed on other websites without prior consent from the author. To download a presentation, simply click this link. If you encounter any difficulties during the download process, it's possible that the publisher has removed the file from their server.

Recommend


More recommend