CONFERENCE ON STANDARADIZATION, CERTIFICATION, QUALITY CONTROL ORDER AND TESTING OF DISTRIBUTION TRANSFORMERS E le c tric a l Re se a rc h a nd De ve lopme nt Assoc ia tion Va doda r a S IAL NT DE CRE S IAL NT DE CRE CRE DE NT
CRE DE NT IAL S
CRE DE NT IAL S
24 c la ssifie d sta te of a rt e va lua tion fa c ilitie s. Ce rtific a tion, c a libra tion, e va lua tion of wide ra ng e of e le c tric a l
produc ts.
E
va lua tion a s pe r na tiona l a nd inte rna tiona l sta nda rds.
T
e c hnolog y De ve lopme nt Ce ntre with thrust on R&D, innova tion a nd ne w produc t de ve lopme nt.
De dic a te d spe c ia lty c e nte r for dia g nostic s of powe r pla nt
e quipme nt.
CRE DE NT IAL S
CRE DE NT IAL S
Re g iona l c e nte rs a t Na vi- Mumba i, Gurg a on a nd Ra ja hmundry-
be tte r c ustome r re a c h a nd se rvic e .
Mobile la bora tory for on- site c ondition monitoring of tra nsforme rs
a nd e ne rg y me te rs.
Ce nte r of e xc e lle nc e for rota ting ma c hine s- fa c ilita te s
improve me nts in de sig n a nd its va lida tion.
Ultra mode rn e va lua tion fa c ility for CRGO a nd insula ting ma te ria ls. L
a rg e st on- line (570 V, 120 kA) short c irc uit la bora tory.
Ac c re dite d by NABL
, BIS, BE E , Inte rte k.
MIL E ST ONE S
Star te d with 1 c e nte r & 2 Produc t te sting 1983
E sta blishe d first Short Circ uit L a b 1998 E sta blishe d la rg e st on line short Circ uit L a b in Savli 2007 E sta blishe d E MI- E MC spe c ia lty c e nte r 2012 E sta blishe d COE for Rota ting ma c hine s 2013 Gr
- wn ove r
40 ye a rs with 24 c e nte rs spre a d
- ve r 5 loc a tions
2015
E RDA’S F ACIL IT Y F OR IS 1180- 2014
ISI ma rking is ma nda tory for tra nsforme rs up to 2.5 MVA a c c ording to
IS 1180- 2014
E
RDA la bora torie s ha ve be e n c a rrying out tra nsforme r te sting sinc e the la st 40 ye a rs.
BIS a c c re dite d DT
T e sting ( a s pe r IS:1180- 2014) L a bora tory a t :
E
RDA Ma ka rpura , Va doda ra (upto 2.5 MVA, 33 KV)
E
RDA (We st), Ra ba le , Na vi Mumba i (upto 200 KVA, 33 KV)
T
e sting Ca pa c ity a t
E
RDA Ma ka rpura , Va doda ra - 140 nos. T ra nsforme rs pe r month
E
RDA (We st) , Ra ba le – 10 nos. T ra nsforme rs pe r month
T
he fa c ilitie s ha ve be e n a c c re dite d by NABL , BIS, BE E (Va doda ra )
T E MPE RAT URE RISE , ROUT INE AND SPE CIAL T E ST F ACIL IT IE S F OR T RANSF ORME RS
E RDA ha s four te st be ds to c a rry out te mpe ra ture rise a nd routine te sts. Ma ximum ra ting of tra nsforme rs whic h c a n be te ste d a t E RDA, Ma ka rpura a re up to a nd inc luding 33 kV, 2500 kVA.
- E
RDA ha s fa c ility to c a rry out Spe c ia l te sts:
- Pr
e ssur e te st
- Ma g ne tic ba la nc e te st
- Ze r
- se que nc e impe danc e
- Ove r fluxing & flux de nsity
- Oil L
e a ka g e te st
- Paint adhe sion te st
- De te r
mina tion of sound le ve l
- BDV & Moisture c onte nt in oil
T E MPE RAT URE RISE T E ST
E RDA
9
SHORT CIRCUIT T E ST F ACIL IT Y AT E RDA
E RDA ha s thre e short c irc uit te st la bora torie s. Ma ximum ra ting of tra nsforme rs whic h c a n be te ste d a t E RDA, Ma ka rpura a re :
11/ 0.433 kV, 1600 kVA 22/ 0.433 kV, 500 kVA 33/ 0.433 kV, 500 kVA
Ma ximum ra ting of tra nsforme r c a n be te ste d a t E RDA, Sa vli a re :
11/ 0.433 kV, 1000 kVA 22/ 0.433 kV, 1000 kVA 33/ 0.433 kV, 4000 kVA
SHORT CIRCUIT T E ST L ABORAT ORY
IMPUL SE T E ST S ON T RANSF ORME RS
E
RDA ha s thr e e Impulse L a bora torie s
2 nos. of 1600 kVp a nd one of
800kVp
Ca n te st up to 160 MVA, 400
kV c la ss tra nsforme rs.
IMPUL SE L ABORAT ORY
E RDA
T RANSF ORME R T E ST F ACIL IT Y AT E RDA (WE ST )
Ac c re dite d by BIS for tra nsforme r te sting a s pe r IS: 1180- 2014 Distribution tra nsforme rs up to 33kV, 200kVA All te sts c a n be c a rrie d out e xc e pt for Short Circ uit T
e st
E
RDA a rra ng e s for the tra nsporta tion to a nd from E RDA (We st) to Va doda ra
E
RDA (We st) c a n c a rry out te sting of 10 tra nsforme rs pe r month
E RDA
14
ROUT INE & T YPE T E ST ING OF T RANSF ORME RS UPT O 100 MVA, 220KV AT SIT E
T
e sts c a rrie d out E RDA’s c a libra te d instrume nts.
DC winding re sista nc e me a sure me nt Me a sure me nt of volta g e ra tio a nd
ve c tor re la tion
L
- a d losse s a nd impe da nc e volta g e
me a sure me nt
No loa d losse s a nd c urre nt
me a sure me nt
Insula tion re sista nc e me a sure me nt T
e mpe ra ture rise
BIS T E ST ING SUMMARY AS PE R IS:1180- 2014 (UPT O 10- 08- 2016)
- Sr. No.
Year Quantity 1 2014-15 5 2 2015-16 125 3 2016-17 113 Report issued 222 Tests in progress 20 Total samples 242
E RDA
16
Re ports for sa mple s in prog re ss will be dispa tc he d by 25- 08- 2016
RAT ING OF T RANSF ORME RS T E ST E D F OR BIS IN 2014- 15
- Sr. No.
kVA Ratings Quantity 1 10 1 2 63 1 3 200 2 Total 4
E RDA
17
RAT ING OF T RANSF ORME RS T E ST E D F OR BIS IN 2015- 16
- Sr. No.
kVA Ratings Quantity 1 10 1 2 16 1 3 25 9 4 63 7 5 100 28 6 160 4 7 200 65 8 315 1 9 400 2 10 500 1 11 630 1 12 1000 1 13 1600 1 14 2500 3 Total 125
E RDA
18
RAT ING OF T RANSF ORME RS T E ST E D F OR BIS IN 2016- 17
- Sr. No.
kVA Ratings Quantity Under Testing
1 5 2
- 2
10 1
- 3
16 11 1 4 25 6 1 6 100 17 3 7 160 4
- 8
200 38 12 9 250 3
- 10
400 1
- 11
500 4 1 12 630 3 2 13 1000 1
- 14
2500 2
- Total
93 20
19
AVE RAGE T IME T AKE N F OR T E ST ING
Sr. Year Time from Receipt of all Clarifications to Dispatch
- f Test Report (Days)
Time from Receipt of Sample to Dispatch of Test Report (Days) 1 2015-16 20 28 2 2016-17 13 18
20
AVE RAGE T IME F OR T E ST ING
Sr. Activity Duration 1 Time taken to allot test dates 2-3 days 2 Time taken to start testing for samples from BIS 2-3 days 3 Time taken to start testing for samples from manufacturers 2-3 weeks 4 Average number of samples tested per month at Vadodara 140 nos 5 Average number of samples tested per month at Rabale 10 nos
21
T E ST ING T IME F OR IS: 1180- 2014
Da y T e sts Da y 1, 2 Routine te sts, Short c irc uit te st, Post routine te sts Da y 3 Impulse te st Da y 4 T e mpe ra ture rise te st Da y 5 Oil le a ka g e te st Da y 6 Air pr e ssur e te st (Routine & T ype te st), Da y 7 F lux de nsity te st, Physic a l ve r ific a tion Da y 8- 12 Re porting
22
T RANSF ORME RS RE CE IVE D F ROM MANUF ACT URE RS (UPT O 10- 08- 2016)
- Sr. No.
Year Quantity 1 2014-15 56 2 2015-16 347 3 2016-17 532 Samples tested 935
23
E RDA’S E XPE RIE NCE : IS 1180
Non c onfor
ma nc e s obse r ve d in following te sts:
- T
e mpe ra ture Rise
- Shor
t Cir c uit
- Impulse te sts
- Pola rity a nd volta g e ra tio
- Induc e d ove r- volta g e te st
- Minimum c le a ra nc e s in a ir
- Construc tiona l re quire me nts a nd fitting s
Ra ting a nd te rmina l ma rking pla te s not provide d Air re le a se plug s Dra in c um sa mpling va lve Ba se c ha nne ls e tc T
a nk la rg e r tha n spe c ifie d in IS for pa rtic ula r ra ting
24
F ACT ORS AT T RI BUT I NG T O DE L AY I N T E ST I NG
Spe c ific a tions a re inc omple te or wrong ly fille d to c a rry out the
te sts.
Spe c ific a tions a re not me e ting the re quire me nts me ntion in
sta nda rd
Misma tc hing of tra nsforme r sr. no in dra wing , te c hnic a l form
a nd on a c tua l tra nsforme r.
Ba sic Insula tion le ve l (kVp) in te st re que st, dra wing &
na me pla te is diffe re nt.
Ac c e ssorie s a re not provide d or do not me e t re quire me nts of
the sta nda rd.
25
F ACT ORS AT T RI BUT I NG T O DE L AY I N T E ST I NG..
Spe c ific a tions a r
e a bove the minimum r e quir e me nts of the sta nda rd.
E
ne rg y L e ve l, te mpe ra ture rise limits e tc .