distributed series reactor
play

Distributed Series Reactor An overview of the conductor impacts of - PowerPoint PPT Presentation

1 Distributed Series Reactor An overview of the conductor impacts of the DSR Joseph Goldenburg, P.E. Mechanical Section Lead and Hardware Manager at NEETRAC 2 Table of Contents DSR Technology Overview History NEETRAC Testing


  1. 1 Distributed Series Reactor An overview of the conductor ‐ impacts of the DSR Joseph Goldenburg, P.E. Mechanical Section Lead and Hardware Manager at NEETRAC

  2. 2 Table of Contents • DSR Technology  Overview  History • NEETRAC Testing • Review of NEETRAC Testing Results

  3. 3 DSR Technology Overview • A multi ‐ dimensional solution to control power flow through existing transmission lines developed by Smart Wire Grid • Increases line impedance by injecting a pre ‐ tuned value of magnetizing inductance of the Single ‐ Turn Transformer • Two modes of operation: Autonomously, based on locally programmable set points 1. Two way communication, enabling more sophisticated operation and 2. line monitoring

  4. 4 DSR Technology History Formation of the Smart Wire Grid, Inc. DSR Prototype (SWG) NEETRAC Gen 1 NEETRAC Gen 2 Testing Testing 2001 ‐ 2008 2009 2010 2011 2012 2013 2014 Initial Patent Formation of the Smart Wire 33 units installed 99 units Filing Focus Initiative (SWFI) at Southern installed at Company TVA

  5. 5 Testing • NEETRAC worked with SWFI to develop tests for the DSR, including:  Clamp slip  Vibration  Impulse  Fault Current  Corona • With the exception of the vibration testing, tests shown are for Gen 2 units.

  6. 6 Testing NEETRAC worked with SWFI to develop tests for the DSR, including:  Clamp slip  Vibration  Impulse  Fault Current  Corona

  7. 7 Clamp Slip Testing Method

  8. 8 Clamp Slip Testing Results

  9. 9 Clamp Slip Testing Results Initial Slip DSR Type Sample ID Sample Test Run Load (lb) 1 445 32013 ‐ 002 ‐ 10 1 2 495 3 518 1 525 1000 32313 ‐ 002 ‐ 10 2 2 520 3 540 1 455 3213 ‐ 003 ‐ 10 3 2 530 3 500 1 620 3213 ‐ 002 ‐ 15 4 2 555 3 700 1 627 1500 32013 ‐ 002 ‐ 15 5 2 648 3 678 1 570 32313 ‐ 001 ‐ 15 6 2 680 3 525

  10. 10 Clamp Slip Testing Takeaways – Post ‐ test inspection of the clamps showed no deformation of the conductor or rods.

  11. 11 Testing • NEETRAC worked with SWFI to develop tests for the DSR, including:  Clamp slip  Vibration  Impulse  Fault Current  Corona

  12. 12 Vibration Testing Methods – Tested in advance of each DSR installation using installation ‐ specific line specifications – So far only tested on Gen 1 DSRs – Tests were based on: • IEEE Std 664 ‐ 1993: IEEE Guide for Laboratory Measurement of the Power Dissipation Characteristics of Aeolian Vibration Dampers for Single Conductors, • IEEE Std 1368 ‐ 2006: IEEE Guide for Aeolian Vibration Field Measurements of Conductors, and • IEEE Std 563 ‐ 1978: IEEE Guide on Conductor Self ‐ Damping Measurements.

  13. 13 Vibration Testing • The purpose of these tests was to understand what happens to the line dynamics when one places an approximately 100 kg mass on the line. • If line dynamics are unacceptable, develop appropriate mitigation strategy.

  14. 14 Vibration Testing Results 4200 lb tension, Unit Placed 6 ft 10 in From Termination No Damper (Config. 13) Damper at 8 ft 6 in (Config. 14) 0.026 0.026 Meter Meter 0.024 0.024 1 1 2 2 0.022 0.022 3 Relat ive Displacement ( in) 3 Relat ive Displacement ( in) 0.020 0.020 0.018 0.018 0.016 0.016 0.014 0.014 0.012 0.012 0.010 0.010 0.008 0.008 0.006 0.006 0.004 0.004 0.002 0.002 0.000 0.000 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 Frequency ( Hz) Frequency ( Hz) Damper at 9 ft ( Config. 15) Damper at 9 ft 6 in (Config. 16) 0.026 0.026 Meter Meter 0.024 0.024 1 1 2 2 0.022 0.022 3 3 Relat ive Displacement ( in) Relat ive Displacement ( in) 0.020 0.020 0.018 0.018 0.016 0.016 0.014 0.014 0.012 0.012 0.010 0.010 0.008 0.008 0.006 0.006 0.004 0.004 0.002 0.002 0.000 0.000 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 Frequency ( Hz) Frequency ( Hz)

  15. 15 Vibration Testing Results

  16. 16 Vibration Testing Takeaways – For TVA line, NEETRAC recommended that: • DSR unit should be installed 6 ft. – 4 in. ± 6 in. from the suspension clamp. • An AFL 1706 damper should be placed 9 ft. ± 6 in. from the DSR face. – Results are relatively consistent across a range of DSR and damper placements so slight deviation from the recommended installation location of the DSR and/or the damper should not affect the damper’s performance.

  17. 17 Testing • NEETRAC worked with SWFI to develop tests for the DSR, including:  Clamp slip  Vibration  Impulse  Fault Current  Corona

  18. 18 Impulse Testing Method – Tested in accordance with IEEE Standard Techniques for High ‐ Voltage Testing – 1995 – 1050 kV BIL selected – Units tested to ensure functionality after impulse testing

  19. 19 Impulse Testing Results Takeaways – Units were functional after impulse testing at 1050 kV – Additional tests scheduled for 1550 kV BIL

  20. 20 Testing • NEETRAC worked with SWFI to develop tests for the DSR, including:  Clamp slip  Vibration  Salt Fog  Impulse  Fault Current  Corona

  21. 21 Fault Current Testing • Method – Tested in accordance with IEEE C37.100.1™ ‐ 2007, IEEE Standard of Common Requirements for High Voltage Power Switchgear Rated Above 1000 V – 63 kA RMS 30 cycle rating selected per Table 3 of IEEE C37.32 – 2002, High Voltage Switches, Bus Supports, and Accessories Schedules of Preferred Ratings, Construction Guidelines, and Specifications

  22. 22 Fault Current Testing Test Sequence

  23. 23 Fault Current Testing Results kA Date DSR Type DSR SN Results (rms) 11/20/2013 1000 32013-001-10-02A-0 68.9 Passed 11/20/2013 1000 32013-003-10-02A-0 69 Passed 11/21/2013 1000 32013-002-10-02A-0 68.4 Passed 11/21/2013 1500 32013-001-15-02A-0 68.8 Passed 11/21/2013 1500 32013-003-15-02A-0 68.6 Passed 11/21/2013 1500 32013-002-15-02A-0 68.8 Passed

  24. 24 Fault Current Testing 02:14.3790372 External Trigger 2 - 1 = 02:14.9541482 566.6483 m 02:14.3874998 1 2 91.1 V Sample_Volt 1 27.74 V 2 -34.17 V Voltage across DSR -102.0 V 215.0 kAmps Sample_Curr_Z 1 -157.7 kAmp 2 -13.58 kAmp Fault Current -186.7 kAmps 02:12.9 2.000s/div 02:24.1

  25. 25 Fault Current Testing 02:14.3790372 External Trigger 02:14.3874998 1 83.39 V Sample_Volt 1 27.74 V 2 -34.17 V Voltage across DSR -102.0 V 215.0 kAmps Fault Current Sample_Curr_ 1 -157.7 kAmp 2 -13.58 kAmp -172.2 kAmps 02:14.3650 10.00 ms/div 02:14.4190

  26. 26 Fault Current Testing Takeaways – Conductor was inspected following completion of testing. There was no visible evidence of test conductor damage.

  27. 27 Testing NEETRAC worked with SWFI to develop tests for the DSR, including:  Clamp slip  Vibration  Impulse  Fault Current  Corona

  28. 28 Corona/RIV Testing • Method – Tested in accordance with IEEE C37.34™ ‐ 1994, IEEE Standard Test Code for High ‐ Voltage Air Switches – Tested with and without protector rod.

  29. 29 Corona/RIV Testing w/ Protector Rod 180 kV Line to Gnd ~ 310 kV Line to Line

  30. 30 Corona Testing w/ Protector Rod The RIV requirement for units installed on 230 kV lines with a 1050 kV BIL rating are less than 500 µV RIV at 156 kV.

  31. 31 Corona/RIV Testing w/o Protector Rod Inception at 296 kV and extinction at 290 kV which are ~ 500 kV Line to Line

  32. 32 Corona Testing • Takeaways – Model 1000 DSRs w/ protector rod passed RIV requirements for 230 kV line, case inception >296 kV line ‐ ground with 11 ft. ground plane. – Model 1000 DSRs w/o protector rod passed RIV requirements for 345 kV line with 11 ft. ground plane (standard allows more distance to ground plane at 345 kV). – Re ‐ design of protector rod may enable corona ‐ free operation above 230 kV when using protector rod.

  33. 33 Conclusion The following tests indicate that DSR type device • should have no impact on the conductor or support structures:  Clamp Slip  Impulse  Fault Current  Corona • The following tests indicate that DSR type device, without mitigation, would have a significant impact on:  Vibration (Note: At TVA and Southern Company, successful mitigation strategies were developed.)

Download Presentation
Download Policy: The content available on the website is offered to you 'AS IS' for your personal information and use only. It cannot be commercialized, licensed, or distributed on other websites without prior consent from the author. To download a presentation, simply click this link. If you encounter any difficulties during the download process, it's possible that the publisher has removed the file from their server.

Recommend


More recommend