Understanding Geomagnetically Induced Currents and Their Impact on the Power Grid: Morgan Substation Neutral Isolation Device (NID) Mike Londo American Transmission Co LLC atcllc.com Wisconsin Public Utility Institute June 2019 Quick


slide-1
SLIDE 1

atcllc.com

Understanding Geomagnetically Induced Currents and Their Impact on the Power Grid:

Morgan Substation Neutral Isolation Device (NID)

Mike Londo American Transmission Co LLC Wisconsin Public Utility Institute June 2019

slide-2
SLIDE 2

atcllc.com

2

Quick Review of where Geomagnetically Induced Currents (GIC) Come From

slide-3
SLIDE 3

atcllc.com

Geomagnetic Induced Currents

EPRI Power Systems Dynamics Tutorial. EPRI, Palo Alto, CA: 2009. 1016042.

slide-4
SLIDE 4

atcllc.com

slide-5
SLIDE 5

atcllc.com

Possible Effects of GIC on ATC System and Equipment

  • Transformer saturation

– Additional heating in transformers--likely – Transformer aging/failure--unlikely

  • Additional VAR (Volts-Amps-Reactive) requirements
  • n system

– Depressed voltages--likely – Voltage collapse on system--depends

  • Harmonics

– Relay misoperation--unlikely – Generator heating--possible but small – Power quality problems--likely but small

slide-6
SLIDE 6

atcllc.com

GIC Isolation Device at Morgan Substation

slide-7
SLIDE 7

atcllc.com

7

Morgan Neutral Isolation Device

slide-8
SLIDE 8

atcllc.com

8

Morgan Neutral Isolation Device cont’d

slide-9
SLIDE 9

atcllc.com

Sequence of Operation

Normal Mode

slide-10
SLIDE 10

atcllc.com

Sequence of Operation

Transitioning to GIC Isolation

slide-11
SLIDE 11

atcllc.com

Sequence of Operation

In GIC Mode

slide-12
SLIDE 12

atcllc.com

Sequence of Operation

Ground Fault in GIC Mode

slide-13
SLIDE 13

atcllc.com

Sequence of Operation

Reset to Normal Mode

slide-14
SLIDE 14

atcllc.com

Critical Development

The Transformation

  • Fail Safe Resilience

– Spark Gap

  • Non consumable
  • Repeatable
  • Inspected after 10 events

– Rogowski Coil (N-G path proof) Located on neutral bar heading to ground

slide-15
SLIDE 15

atcllc.com

15

Morgan NID in “By-Pass” Mode

10kv spark gap

slide-16
SLIDE 16

atcllc.com

16

Questions?