SLIDE 6 CODES AND STANDARDS
1. WHERE DOCUMENTS ARE REFERENCED IN THE GENERAL AND DESIGN NOTES, THEY SHALL BE THE LATEST APPLICABLE EDITIONS, UNLESS OTHERWISE NOTED. 2. ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF THE 2015 INTERNATIONAL BUILDING CODE, INCLUDING REFERENCE STANDARDS, ADDENDA AND APPENDICES. 3. IN ADDITION, THE FOLLOWING CODES, STANDARDS AND SPECIFICATIONS SHALL APPLY WHERE MORE STRINGENT AND AS MODIFIED BY THE BUILDING CODE: A. ACI 318 "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE AND COMMENTARY" B. ACI 530/530.1 "BUILDING CODE REQUIREMENTS AND SPECIFICATIONS FOR MASONRY STRUCTURES AND RELATED COMMENTARIES" C. AISC "STEEL CONSTRUCTION MANUAL" AND AISC 360 "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS" D. AISC "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES" E. AISC "SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A 325 OR A 490 BOLTS" F. AWS D1.1 "STRUCTURAL WELDING CODE" G. AWS D1.4 "STRUCTURAL WELDING CODE-- REINFORCING STEEL" H. AISI "SPECIFICATION FOR THE DESIGN OF COLD FORMED STEEL STRUCTURAL MEMBERS"
PROJECT DOCUMENTS
1. THIS SET OF DRAWINGS, TOGETHER WITH THE SPECIFICATIONS, CONSTITUTES THE COMPLETE DOCUMENT BY WHICH ALL WORK IS TO BE CARRIED OUT. 2. THE CM/GC SHALL VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS AT THE JOB SITE. THE CM/GC SHALL USE STRUCTURAL DRAWINGS IN CONJUNCTION WITH ARCHITECTURAL, CIVIL, MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION AND ALL OTHER RELEVANT CONSULTANTS' DRAWINGS BEFORE COMMENCING WITH THE WORK AND SHALL NOTIFY THE FRA CONSTRUCTION COORDINATOR OF ANY DISCREPANCIES REQUIRING CLARIFICATION OR REVISION. 3. SCALES NOTED ON THE DRAWINGS ARE FOR GENERAL INFORMATION ONLY. NO DIMENSIONAL INFORMATION SHALL BE OBTAINED BY SCALING FROM THE DRAWINGS. 4. IN THE EVENT THAT CERTAIN DETAILS OF THE CONSTRUCTION ARE NOT FULLY SHOWN OR NOTED ON DRAWINGS, THEIR CONSTRUCTION SHALL BE OF THE SAME TYPE AS FOR SIMILAR CONDITIONS THAT ARE SHOWN OR NOTED, SUBJECT TO THE STRUCTURAL ENGINEER'S [PRIOR WRITTEN] APPROVAL. 5. REFER TO ARCHITECTURAL DRAWINGS FOR THE FOLLOWING: A. SIZE AND LOCATION OF ALL DOOR OPENINGS, EXCEPT AS NOTED. B. SIZE AND LOCATION OF ALL INTERIOR NON-BEARING PARTITIONS. C. DIMENSIONS NOT SHOWN ON STRUCTURAL DRAWINGS. 6 REFER TO MEP DRAWINGS FOR THE FOLLOWING: A. PIPE AND DUCT RUNS, SLEEVES, HANGERS, TRENCHES, WALL AND SLAB OPENINGS, EXCEPT AS SHOWN OR NOTED. B. SIZE AND LOCATION OF MACHINE OR EQUIPMENT BASES, ANCHOR BOLTS FOR MOTOR MOUNTS, EXCEPT AS SHOWN OR NOTED.
REINFORCED CONCRETE
1. STRUCTURAL CONCRETE STRENGTHS AND TYPES USED IN THIS PROJECT SHALL BE AS FOLLOWS UNLESS NOTED OTHERWISE: CALL OUT IN DOCUMENTS f'c (PSI) AGGREGATE STANDARD CONCRETE 5000 NORMAL WEIGHT 2. ALL CONCRETE MIXES SHALL COMPLY WITH THE REQUIREMENTS OF THE BUILDING CODE AND THE ACI 318. MIX DESIGNS FOR EACH TYPE AND STRENGTH SHALL BE PREPARED BY CM/GC AND TESTED BY AN INDEPENDENT TESTING LABORATORY. THE MIX DESIGNS SHALL THEN BE SUBMITTED TO THE FRA FOR REVIEW AND APPROVAL. 3. PORTLAND CEMENT SHALL CONFORM TO ASTM C150. WHERE CONCRETE IS IN CONTACT WITH ROCK, THE TYPE OF EXPOSURE SHALL DETERMINE THE CEMENT TYPE. THE CONTRACT REQUIREMENT IS FOR ALL CONCRETE IN CONTACT WITH ROCK TO MEET: MODERATE SULFATE EXPOSURE TYPE II 4. NORMAL WEIGHT AGGREGATE SHALL CONFORM TO THE REQUIREMENTS OF ASTM C33. 1. SUBGRAGE BELOW STRUCTURAL SLABS (INCLUDING MUD SLABS) SHALL CONSIST OF EITHER BLOWN ROCK OR COMPACTED FILL, MEETING THE FOLLOWING: A. BLOWN ROCK: SHALL CONSIST OF UNDISTURBED NATIVE ROCK WITH ALL LOOSE MATERIAL AND DEBRIS REMOVED SO THAT ONLY SOUND ROCK REMAINS. THE SURFACE SHALL BE SUITABLY CLEANED OF ANY FOREIGN SUBSTANCES RESULTING IN A CLEAN SURFACE SUITABLE TO RECEIVE CONCRETE OR ANY OTHER UNDERSLAB SYSTEM WHICH OCCUR. B. COMPACTED FILL: SHALL CONSIST OF COMPACTED FILL MATERIAL AND SPOILS IN ACCORDANCE WITH THE GEOTECHNICAL RECOMMENDATIONS (SEE CIVIL DRAWINGS), BUILT UP TO AN ELEVATION SUITABLE TO RECEIVE THE CONCRETE SLAB AND ANY OTHER UNDERSLAB SYSTEMS WHICH OCCUR. 2. UNLESS NOTED OTHERWISE, SUBGRADE PREPARATION SHALL BE AS FOLLOWS: A. EXPERIMENT CAVERNS: BLOWN ROCK B. ALL OTHER LOCATIONS: COMPACTED FILL
SUBGRADE PREPARATION
6. THE PROJECTING CORNERS OF COLUMNS, BEAMS, WALLS, ETC. SHALL BE FORMED WITH 3/4 INCH CHAMFER, UNLESS OTHERWISE NOTED ON ARCHITECTURAL DRAWINGS. 7. CONSTRUCTION JOINTS SHALL BE DOWELLED, KEYED AND THE SURFACES SHALL BE CLEANED AND LAITANCE REMOVED. ALTERNATIVELY, WHERE APPROVED BY FRA, PROVIDE JOINTS CLEANED AND ROUGHENED TO 1/4 INCH AMPLITUDE BY MECHANICAL METHODS. 8. LOCATION OF CONSTRUCTION JOINTS SHALL BE AS INDICATED ON STRUCTURAL DRAWINGS. PROVIDE WATERSTOPS FOR ALL CONSTRUCTION JOINTS BELOW WATER TABLE OR AS INDICATED IN DETAILS. ADDITIONAL CONSTRUCTION JOINTS MAY BE ADDED ONLY WITH APPROVAL OF ARCHITECT AND FRA. 9. REINFORCING BARS SHALL CONFORM TO THE REQUIREMENTS OF ASTM A615, GRADE 60. UNLESS NOTED OTHERWISE. REINFORCING BARS, WHICH ARE TO BE WELDED, SHALL CONFORM TO APPLICABLE ASTM AND AWS SPECIFICATIONS. 11. ALL REINFORCING BARS MARKED "CONTINUOUS" SHALL BE TENSION SPLICED, UNLESS OTHERWISE SHOWN ON DRAWINGS. 12. ALL BARS AT NON-CONTINUOUS ENDS SHALL HAVE A STANDARD HOOK. 13. PROVIDE DEVELOPMENT AND SPLICES OF REINFORCEMENT ACCORDING TO THE TYPICAL DETAIL TABLES. 14. ALL DOWELS SHALL BE FULLY DEVELOPED IN TENSION, UNLESS OTHERWISE NOTED. 15. DOWEL TO WALLS AND COLUMNS SHALL MATCH THE CORRESPONDING REINFORCING OF THE WALL OR COLUMN. 16. MINIMUM LAP OF WELDED WIRE FABRIC SHALL BE 6 INCHES OR ONE FULL MESH, WHICHEVER IS GREATER. 18. ALL REINFORCING STEEL SHALL BE SECURELY HELD IN ORDER TO MAINTAIN ITS POSITION WHILE CONCRETE IS POURED. CHAIRS, TIES, SPACERS, ADDITIONAL BARS AND STIRRUPS,
- ETC. SHALL BE PROVIDED BY THE CM/GC.
19. CM/GC SHALL COORDINATE AND INSTALL ALL REQUIRED EMBEDDED ITEMS, SLEEVES, POCKETS, ETC. PRIOR TO CONCRETE PLACEMENT. REFER TO TYPICAL DETAILS OF PENETRATIONS FOR LIMITATIONS ON THEIR POSITIONING IN RESPECT TO REINFORCING. DO NOT CUT ANY REINFORCING THAT MIGHT INTERFERE WITH EMBEDDED ITEMS PLACEMENT. 20. MECHANICAL PIPES AND/OR ELECTRICAL CONDUITS SHALL NOT PASS THROUGH CONCRETE COLUMNS AND BEAMS, UNLESS SPECIFICALLY DETAILED ON DRAWINGS. 21. NO ALUMINUM SHALL BE EMBEDDED IN CONCRETE. 22. CM/GC SHALL NOTIFY FRA CONSTRUCTION COORDINATOR, 24 HOURS BEFORE POURING OF CONCRETE, FOR INSPECTION OF REINFORCEMENT LAYOUT. NO CONCRETE SHALL BE POURED UNLESS ALL REINFORCEMENT AND INSTALLATIONS HAVE BEEN INSPECTED AND APPROVED BY THE FRA CONSTRUCTION COORDINATOR. 23. CONCRETE CAST ON SLOPED SURFACES SHALL BEGIN AT THE LOWEST ELEVATION AND CONTINUE MONOLITHICALLY TOWARD THE HIGHER ELEVATION. 5. CONCRETE FORMS SHALL BE LAID OUT AND CONSTRUCTED TO PROVIDE THE SPECIFIED CAMBERS INDICATED ON THE STRUCTURAL DRAWINGS, AND SHALL COMPLY WITH REQUIREMENTS OF ACI 318. 17. POLYPROPYLENE MACROSYNTHETIC FIBER REINFORCING SHALL CONFORM TO ASTM C1116 (TYPE III). 10. REINFORCING BARS DENOTED AS "GFRP" SHALL BE SOLID ROUND GLASS FIBER REINFORCED POLYMER BARS CONFORMING TO ASTM D7957.
GENERAL
1. FOR CLARITY THE PREFIX SHEET NUMBER "UG-FD-" HAS BEEN REMOVED FROM ALL SECTION AND CALLOUT SYMBOLS. ALL SECTIONS AND CALLOUTS IN THIS PACKAGE REFER TO THE "UG-FD-SS-XXXX" SHEETS. 24. NO JOINTS IN SLAB. BRUSH-IN CEMENT AT APPROX 6-12 WEEKS AFTER CASTING PRIOR TO TRAFFICKING. 2. ALL TOP OF SLAB ELEVATIONS ARE RELATIVE TO 4850 LEVEL AND ARE INDICATED AS: T/SL = XXX' - XX X/X"
EXPANSION ANCHORS AND ADHESIVE ANCHORS
1. ALL EXPANSION ANCHOR AND ADHESIVE ANCHOR PRODUCTS SHALL BE SUBMITTED FOR REVIEW PRIOR TO USE. SUBMITTALS SHALL CONTAIN APPLICABLE PRODUCT LITERATURE AND AN ICC-ES EVALUATION REPORT. 2. ALL EXPANSION ANCHORS AND ADHESIVE ANCHORS INSTALLED BE IN ACCORDANCE WITH THE MANUFACTURER REQUIREMENTS. SPECIAL INSPECTION AS STIPULATED IN THE APPLICABLE ICC-ES REPORT AND IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE. 3. EPOXY ANCHORS INSTALLED HORIZONTALLY OR AT AN UPWARDLY INCLINED ANGLE (INCLUDING VERTICAL) SHALL BE INSTALLED BY PERSONNEL CERTIFIED BY AN APPLICABLE CERTIFICATION PROGRAM, SUCH AS THE ACI/CRSI ADHESIVE INSTALLER CERTIFICATION PROGRAM, OR AN APPROVED EQUIVALENT, AND SHALL HAVE CONTINUOUS SPECIAL INSPECTION.
STRUCTURAL STEEL
1. ALL STEEL MEMBERS SHALL BE HOT-DIP GALVANIZED ACCORDING TO ASTM A123. 2. STRUCTURAL STEEL SHALL BE PROVIDED AS FOLLOWS: SHAPE ASTM STANDARD Fy (KSI) WIDE FLANGES A992 50 CHANNELS A36 36 HSS (RECTANGULAR AND SQUARE) A500 GRADE C 46 HSS (ROUND) A500 GRADE C 46 PIPES A53 GRADE B 35 ANGLES A36 36 PLATES A36 36 TEES A992 50 Fy IS THE MINIMUM TENSILE YIELDING STRESS TO BE PROVIDED UNLESS OTHERWISE NOTED. 3. ALL BOLTED CONNECTIONS SHALL BE MADE WITH HIGH STRENGTH BOLTS CONFORMING TO ASTM A325 OR ASTM A490. ALL CONNECTIONS SHALL BE TYPE N UNLESS OTHERWISE NOTED ON DRAWINGS. FASTENERS AND CONNECTING PARTS SHALL BE HOT-DIP GALVANIZED ACCORDING TO ASTM A153. BOLTS DENOTED AS A325-SC OR A490-SC SHALL BE SLIP CRITICAL. 4. NUTS SHALL CONFORM TO ASTM A563, DH OR ASTM A194, 2H. PROVIDE WASHERS CONFORMING TO ASTM F436 AT EACH THREADED ROD OR BOLT. NUTS AND WASHERS SHALL BE HOT-DIP GALVANIZED ACCORDING TO ASTM A153. 5. BOLT HOLES IN STEEL MEMBERS, WITH THE EXCEPTION OF BASE PLATES, SHALL BE 1/16 INCH LARGER IN DIAMETER THAN THE NOMINAL SIZE OF BOLT USED, UNLESS NOTED OTHERWISE ON DRAWINGS. 6. BOLT HOLES IN STEEL BASE PLATES SHALL BE OF THE SIZE MARKED ON DRAWINGS. PROVIDE WELDED PLATE WASHERS 3"x 3"x 3/8" THICK MINIMUM. 7. ANCHOR BOLTS SHALL BE ROUND BAR STOCK, THREADED, CONFORMING TO ASTM F1554, GRADE 36 UNLESS OTHERWISE NOTED. ANCHOR BOLTS SHALL BE SUPPLIED WITH CORRESPONDING NUTS AND WASHERS. ANCHOR BOLTS SHALL BE HOT-DIP GALVANIZED. 8. STRUCTURAL THREADED RODS SHALL HAVE THREADS CONFORMING TO UNC CLASS 2A (EXTERIOR THREADS) AND 2B (INTERNAL THREADS). THREADED RODS SHALL BE HOT-DIP GALVANIZED. 9. WELDING MATERIALS SHALL CONFORM TO AWS D1.1. ELECTRODES SHALL HAVE A MINIMUM TENSILE STRENGTH OF 70 KSI AND BE LOW-HYDROGEN TYPE. 10. WELD LENGTHS CALLED FOR ON PLANS ARE THE NET EFFECTIVE LENGTHS REQUIRED. 11. AT PARTIAL PENETRATION WELDS THE SIZE GIVEN IS THE MINIMUM EFFECTIVE THROAT. FABRICATOR SHALL PROVIDE PROPER JOINT PREPARATION TO ACHIEVE THE MINIMUM EFFECTIVE THROAT AS REQUIRED BY THE AWS CODE. 12. SPLICES SHALL BE DESIGNED TO DEVELOP THE FULL CAPACITY OF THE MEMBER AT THE POINT OF SPLICE. SPLICES SHALL BE MADE ONLY AT LOCATIONS INDICATED ON DRAWINGS. FULL DETAIL AND BACK-UP CALCULATIONS OF SPLICES REQUIRE REVIEW AND APPROVAL BY THE ENGINEER. 13. SHAPE AND SIZE GUSSET PLATES IN SUCH A MANNER AS TO CLEAR ALL ARCHITECTURAL FINISHES AND MECHANICAL FIXTURES (DUCTS, PIPES, ETC.). SUBMIT THE CONFIGURATION OF ALL GUSSET PLATES EXPOSED TO VIEW TO ARCHITECT AND ENGINEER FOR REVIEW AND APPROVAL. 14. CM/GC SHALL PROVIDE ALL NECESSARY TEMPORARY BRACING, GUYING AND CONNECTING MEMBERS REQUIRED TO ERECT THE STRUCTURE, MAINTAIN CORRECT ALIGNMENT AND SAFELY RESIST ALL POSSIBLE COMBINATIONS OF DEAD, CONSTRUCTION, ERECTION, WIND AND OTHER LATERAL LOADS. 15. REFER TO SPECIFICATIONS FOR STEELWORK PROTECTION AND COATINGS.
STEEL FRAMING NOTES
1. STEEL MEMBERS ARE ASSUMED TO BE DIMENSIONED TO THEIR CENTERLINE UNLESS OTHERWISE INDICATED. STEEL COLUMNS ARE ASSUMED TO BE PLUMB AND STEEL BEAMS ARE ASSUMED TO BE LEVEL UNLESS OTHERWISE INDICATED. 2. STEEL MEMBERS NOT LOCATED IN PLAN BY A DIMENSION LINE SHALL BE EQUALLY SPACED BETWEEN DIMENSIONED MEMBERS. 16. CLEAN AREAS IN ALL LOCATIONS WHERE GALVANIZING IS DAMAGED OR MISSING AND REPAIR GALVANIZING TO COMPLY WITH ASTM A780/A780M. GALVANIZING TO BE REPAIRED AT ALL LOCATIONS WHERE FIELD WELDING IS REQUIRED.
STRUCTURAL STEEL CONNECTIONS
1. ALL FASTENERS AND CONNECTING PARTS SHALL BE HOT-DIP GALVANIZED ACCORDING TO ASTM A153, EXCEPT A490 BOLTS, WHICH SHALL HAVE A ZINC/ALUMINUM CORROSION PROTECTIVE COATING IN ACCORDANCE WITH F 1136 GRADE 3. 2. CM/GC SHALL PROVIDE THE DETAILING FOR ALL STRUCTURAL STEEL CONNECTIONS NOT COMPLETELY DEFINED IN THE DRAWINGS. CM/GC SHALL RETAIN A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF SOUTH DAKOTA TO DETAIL SUCH CONNECTIONS. 3. REFER TO STEEL CONNECTION TYPICAL DETAILS FOR STEEL CONNECTION REQUIREMENTS, MINIMUM REACTIONS AND ADDITIONAL INFORMATION.
SHOTCRETE, GROUT, AND ROCK BOLTS
1. REFER TO C-002, CIVIL GENERAL NOTES, FOR SHOTCRETE, GROUT, AND ROCK REINFORCEMENT.
MISCELLANEOUS METALS
1. ALL STEEL AND METAL ITEMS AND ELEMENTS NOT SHOWN ON STRUCTURAL DRAWINGS SHALL BE DEFINED AS MISCELLANEOUS METALS. 2. FOR SCOPE OF WORK RELATED TO ALL MISCELLAEOUS METALS, THE REQUIREMENTS OF SPECIFICATION SECTION 05500 APPLY.
Arup USA Inc 77 Water Street, New York NY 10005, T 212 896 3000 www.arup.com
DRAWING NO.
SCALE:
REV. REVISIONS DESIGNED DRAWN CHECKED DESCRIPTION DATE REV.
Fermilab
Long-Baseline Neutrino Facility 02/08/19
2/8/2019 6:33:31 PM
3
15-1-6 UG-FD-SS-010
UNDERGROUND
LBNF - FSCF - EXCAVATION
IB AF KS ARUP ARUP ARUP
STRUCTURAL GENERAL NOTES
N.T.S.
1 07/27/18 30% FD SUBMISSION 2 11/02/18 60% FD SUBMISSION 3 02/08/19 90% FD SUBMISSION