1
Centralized and Decentralized Control for Demand Response Project - - PowerPoint PPT Presentation
Centralized and Decentralized Control for Demand Response Project - - PowerPoint PPT Presentation
Centralized and Decentralized Control for Demand Response Project team: Shuai Lu (PI) Harold Kirkham Presented by: Nader Samaan Ruisheng Diao Shuai Lu Marcelo Elizondo Chunlian Jin Ebony Mayhorn Yu Zhang Energy and Environment Seminar
Outline
Concept of demand response Types of demand response programs Centralized and decentralized control in existing power systems Models to simulate the effects of demand response Comparing the two control philosophies Concluding remarks
Defining Demand Response
An earlier definition by FERC (2008)[1]:
A reduction in the consumption of electric energy by customers from their expected consumption in response to an increase in the price of electric energy or to incentive payments designed to induce lower consumption of electric energy.
Newer definition by FERC (2010)[2]:
“demand response” includes consumer actions that can change any part of the load profile of a utility or region.
smart appliances or devices that can respond automatically to the signals from utility or changes of power system condition. smart integration of changeable consumption with variable generation (wind and solar) manage demand as needed to provide grid services such as regulation and reserves
[1] Wholesale Competition in Regions with Organized Electric Markets, FERC Order No. 719, October 2008 [2] National Action Plan on Demand Response. FERC, June 2010
Type of Demand Response Programs
FERC DR Categorization [3]:
Type 1: dynamic pricing without enabling technologies (manual response to price signal) Type 2: dynamic pricing with enabling technologies (automatic response to price signal) Type 3: direct load control Type 4: interruptible tariffs Type 5: demand response programs operated by Independent System Operators (ISO) or utilities (providing various reserves for the system)
Another category that need to be added:
Type 6: autonomous load response to frequency and voltage
4
[3] A National Assessment of Demand Response Potential, FERC, June 2009
Group DR Programs Based on Control Approaches
5
Grouping Criteria Location where the information is from Local Center Location where the response decision is made Local Type 6 *Types 1 & 2 Central Types 3, 4 & 5
*If the price is generated through an auction process, in which both generation and demand submit bids in real time to get a market clearing price, then DR Type 1 and 2 could be considered decentralized control. Otherwise, if the price signal is “designed” by the system operator according to certain physical variables of the system, Type 1 and 2 could be considered a combination of centralized and decentralized control,
Centralized and Decentralized Control in Existing Power Systems
Purpose of controls
To maintain system voltages and frequency and other system variables within their acceptable limits, in response to normal load and generation variations as well as large disturbances.
Centralized controls
Generation scheduling and dispatch Automatic generation control for frequency regulation Real and reactive power flow adjustments to resolve congestions or reduce loss
Decentralized controls
Generator governor response Automatic voltage regulation Protection relays
6
A Test Platform for Demand Response Control Approaches
7
800 806 808 812 814 810 802 850 818 824 826 816 820 822 828 830 854 856 852 832 888 890 838 862 840 836 860 834 842 844 846 848 864 858
Modified IEEE 34 bus test feeder: Lumped loads were replaced by 147 detailed household load models; A load factor of 40% was assumed to determine the number of households.
8
Water Heater Model
8
24.000 19.200 14.400 9.6000 4.8000- 0.0000
- 0.0000
- 0.0000
- 0.001
Water temperature Active power Water flow Electric power Water temperature
9
Air Conditioning Model
9
10000.0 8000.0 6000.0 4000.0 2000.0 0.0000 [s] PQ Measurement: Active Power in p.u. 10000.0 8000.0 6000.0 4000.0 2000.0
- 0.0000
[s] 84.00 83.00 82.00 81.00 80.00 House Common Model: To 10000.0 8000.0 6000.0 4000.0 2000.0
- 0.0000
[s] 3.00 2.00 1.00 0.00
- 1.00
House Common Model: p 10000 0 8000 0 6000 0 4000 0 2000 0 0 0000 [s] 79.00 78.00 77.00 76.00 75.00 74.00 73.00
Outdoor temperature Active power Indoor temperature Equivalent Thermal Parameters Circuit
10
Ten Types of House Load Representing Other Appliances
10
site Residence Size Occupants_ number 28 2965 4 60 3156 3 100 2510 3 110 1518 2 250 1248 2 344 4119 6 361 2416 4 364 868 1 483 1988 2 500 2676 3
Information of the 10 types house
Other appliances data is taken from ELCAP load data set
11
Single House Model
11
A/C Water Heater Other appliances
Response Mechanisms in the Household Load Model
All demand responses come from A/C units and water heaters, i.e., thermostat-controlled loads. Centralized control
Proportional controllers for temperature settings adjustment Direct on/off control Communication delays are added
Decentralized control
Bang-bang controllers for frequency, voltage and price responses
12
Simulations of the Two Control Approaches
Two types of DR functions were simulated:
Response to power system frequency dip Balancing generation and load (regulation and load following services)
The modified IEEE 34 bus feeder is connected to the IEEE 39 bus transmission system model to simulate frequency response. Regulation signal from a balancing authority and wind power derived from actual wind data were used to test balancing services.
13
14 14
Project: Graphic: 39-bus_grid RMS-Simulation,balanced 10:000 s Nodes Line to Line Positive-Sequence Voltage, Magnitude [kV] Li G d P i i S V l M i d [ ]
Main
67.588 0.980 3.545
Station7/B7 94.895
0.949
- 5.534
Station6/B6 96.846
0.968
- 2.404
Station5/B5 96.399
0.964
- 3.159
Station4/B4 96.578
0.966
- 3.130
Station3/B3 99.319
0.993
- 1.878
Station2/B2 101.18..
1.012
- 0.543
Station29/B29 103.80..
1.038 9.201
Station28/B28 103.53..
1.035 6.314
- n1/B1 93.394
0.934
- 12.73..
Station27/B27 100.91..
1.009 0.974
Station26/B26 102.90..
1.029 2.367
Station25/B25 103.61..
1.036 1.652
Station24/B24 100.10..
1.001 4.855
Station23/B23 101.97..
1.020 13.489
Station22/B22
102.84.. 1.028 13.703
Station21/B21 100.09..
1.001 8.024
Station20/B20 102.99..
1.030 11.454
Station19/B19 100.52..
1.005 11.745
Station18/B18 99.429
0.994 0.014
Station17/B17 99.785
0.998 1.877
Station16/B16 99.466
0.995 4.385
Station15/B15 97.808
0.978 1.860
Station14/B1497.607
0.976
- 0.282
Station13/B13 98.225
0.982 0.924
Station12/B12 96.753
0.968 0.498
Station11/B11 97.894
0.979 0.177
Station10/B10 98.661
0.987 1.469
tation9/B9 91.945
0.919
- 14.99..
Station8/B8 94.367
0.944
- 6.522
2-W inding..
2.01 0.64 78.96
- 2.01
- 0.47
78.96
Load21
262.21 110.05
Load8
471.21 158.88
Load39
841.00 190.44
G ~ G10
250.38 348.98 28.63
G ~ G9
845.63 68.21 98.08
G ~ G8
608.67 73.71 101.01
G ~ G7
634.98 127.45 98.13
G ~ G6
785.23 361.17 110.10
G ~ G5
570.26
- 74.59
104.57
G ~ G4
713.06 362.37 111.87 740.65 345.69 102 17
G ~ G2
523.80 337.93 92.35
G ~ G1 Trafo9
845.63 68.21 92.27
- 840.1..
39.37 92.27
L28-29
- 356.3..
9.96 199.37 357.98
- 18.76
199.37
L26-28
- 154.2..
- 35.57
88.96 155.20
- 36.90
88.96
L25-26
38.55
- 53.33
36.92
- 38.49
- 0.71
36.92
L26-27
- 182.8..
- 129.3..
128.15 183.53 111.22 128.15
L17-27
- 86.30
56.97 71.06 86.47
- 87.18
71.06
Trafo8
608.67 73.71 92.32
- 606.5..
9.82 92.32
L2-25
- 416.9..
54.22 241.01 429.08
- 54.61
241.01
Trafo10
- 250.3..
- 318.5..
27.36 250.38 348.98 27.36
L16-24
143.75 98.58 102.78
- 143.6..
- 103.5..
102.78
Trafo6
- 785.2..
- 263.7..
103.20 785.23 361.17 103.20
L23-24
- 437.3..
- 10.86
252.32 441.56 40.83 252.32
Trafo7
634.98 127.45 88.75
- 633.0..
- 22.48
88.75
L22-23
46.47 81.25 62.27
- 46.41
- 99.66
62.27
L21-22
- 734.3..
- 131.5..
430.38 738.76 182.46 430.38
Trafo19-2..
- 47.72
- 234.1..
28.94 48.15 242.49 28.94
Trafo4
713.06 362.37 107.60
- 708.5..
- 269.8..
107.60
Trafo5
570.26
- 74.59
95.16
- 567.3..
133.26 95.16
L16-19
660.36 27.41 379.63
- 653.4..
26.69 379.63
L16-21
470.12 20.86 272.07
- 468.3..
- 16.30
272.07
L17-18
- 393.6..
- 9.75
228.69 394.78 9.52 228.69
L3-18
- 243.8..
5.51 142.42 244.53
- 18.57
142.42
L16-17
482.93
- 69.64
283.24
- 481.2..
77.66 283.24
L15-16
- 467.2..
- 125.8..
285.67 469.45 132.04 285.67
L14-15
- 163.7..
- 9.82
97.64 164.30
- 19.00
97.64
L13-14
- 203.3..
- 47.72
123.55 203.74 35.74 123.55
Trafo12-1..
- 17.79
- 44.59
5.87 17.83 45.67 5.87
Trafo11-1..
- 10.69
39.09 4.87 10.72
- 38.35
4.87
Trafo3
- 740.6..
- 206.6..
104.24 740.65 345.69 104.24
L10-13
221.79 76.81 138.76
- 221.5..
- 81.42
138.76
L10-11
518.85 129.79 313.97
- 517.6..
- 124.1..
313.97
L3-4
105.85 111.50 98.74
- 105.5..
- 127.0..
98.74
L4-5
4.53 7.02 11.99
- 4.53
- 19.49
11.99
L2-3
164.70 99.27 117.98
- 164.2..
- 119.2..
117.98
L1-2
- 492.6..
- 113.6..
312.52 502.61 165.01 312.52
L1-39
- 489.5..
- 100.9..
321.03 492.60 113.65 321.03
L9-39
352.98 28.98 232.90
- 351.4..
- 89.47
232.90
L8-9
356.37 49.53 222.40
- 352.9..
- 28.98
222.40
L5-6
- 482.9..
- 127.7..
299.19 483.47 130.62 299.19
L5-8
- 485.2..
- 129.1..
307.19 487.46 147.19 307.19
L7-8
342.92 78.65 215.01
- 342.3..
- 79.28
215.01
L6-7
557.42 178.59 350.74
- 555.2..
- 155.1..
350.74
L6-11
- 526.2..
- 73.63
316.79 528.37 85.06 316.79
Trafo2
514.63 333.35 89.34
- 514.6..
- 235.5..
89.34
L26-29
- 201.9..
- 38.73
116.53 204.18
- 46.98
116.53
L4-14
- 365.9..
- 51.77
220.95 367.12 57.54 220.95
Load4
466.93 171.83
Load3
302.21 2.25
Load18
149.15 28.32
Load25
215.92 45.50
Load26
134.11 16.40
Load27
269.19 72.33
Load28
201.11 26.95
Load29
277.96 26.37
Load24
293.61
- 87.72
Load15
302.97 144.86
Load16
313.04 30.73
Load23
237.91 81.32
Load20
615.05 100.88
Load12
7.07 82.94
Load31
9.17 4.59
Load7
212.29 76.53 DIgSILENT
Connection to test feeder Connection to test feeder Under- frequency event Under- frequency event Under- voltage event Under- voltage event
Simulation with Transmission network IEEE 39 bus system with 10 generators, total generation around 6.18 GW IEEE 34 bus system
Frequency Event Created
15
10 20 30 40 50 60 59.2 59.4 59.6 59.8 60 60.2 Time (min) Frequency (Hz)
Frequency dip created by tripping generator 1, a large generator in the IEEE 39 bus system. Loads at buses 20, 8 and 39 were disconnected to simulate the recovery of the system frequency.
Frequency Response Provided by DR
16 10 20 30 40 50 60 1500 2000 2500 3000 3500 Total Feeder Load Time (min) Active Power (kW) DR to frequency event @ 6min Base case (no frequency event)
10 20 30 40 50 60 2000 2500 3000 3500 Total Feeder Load Time (min) Active Power (kW) DR to 5 degF temp setting change Base Case
Centralized control: Assuming 20 seconds delay by devices and 2 min delay by operators [4]. Decentralized control: Frequency thresholds 59.4 and 59.94 Hz.
[4] Demand Response Spinning Reserve Demonstration, LBNL-62761, Lawrence Berkeley National Laboratory, May 2007
Initialization period of A/C and water heaters
DR Following Regulation Signals
17 10 20 30 40 50 60 2200 2400 2600 2800 3000 3200 3400 Total Feeder Load Time (min) Active Power (kW) DR to regulation signal Base case 10 20 30 40 50 60
- 200
200 400 Regulation Signal Time (min) Active Power 10 20 30 40 50 60
- 300
- 200
- 100
100
Feeder Load Reduction
Time (min) Active Power
Feeder load Regulation signal and demand response providing regulation: Assuming 5 sec communication delay
DR Following Wind Power Variations
Water heaters and A/C units following wind power variation: Assuming 5 sec communication delay Control law: ΔTset = k•Reg With constraints on Tset and ΔTset
10 20 30 40 50 60 0.0105 0.011 0.0115 0.012 Regulation Signal Time (min) Active Power (pu) 10 20 30 40 50 60
- 1000
- 500
500 Feeder Load Reduction Time (min) Active Power (kW)
Regulation Signal Derived from Wind Power Output
Predictability of DR under Centralized Control
19
10 20 30 40 50 60 2000 2200 2400 2600 2800 3000 3200 3400 Total Feeder Load Time (min) Active Power (kW) 1 degF temperature setting change 2 degF temperature setting change 3 degF temperature setting change 5 degF temperature setting change Base case
Feeder load change as a function of changes in temperature settings (ΔTset )
Predictability of DR under Centralized Control
20
1 2 3 5 100 200 300 400 Temperature Setting Change (degF) Active Power (kW) Max Feeder Load Reduction
144.44 194.69 216.72 291.20
1 2 3 5 50 100 150 Temperature Setting Change (degF) Energy (kWh) Energy of temperature setting change from base case
34.03 56.66 74.06 113.33
Load reduction (max kW) as a function of changes in temperature settings Load reduction (kWh in 60-minute simulation) as a function of changes in temperature settings
Predictability of DR under Decentralized Control
21
10 20 30 40 50 60 1500 2000 2500 3000 3500 Total Feeder Load Time (min) Active Power (kW) DR to frequency event @ 6min Base case (no frequency event)
Reduction caused by frequency response Reduction caused by voltage response
Comparison of the Characteristics of Two Control Philosophies
Response time
Decentralized control is much faster and suitable for improving system frequency response or resolving frequency and voltage stress of the system. Centralized control is slower and can not follow the fast changes of regulation signal but is suitable for load following service and spinning reserve.
Predictability
Response from decentralized control is more complicated and harder to predict. Response from centralized control is close-to-linear, in terms of load change vs. temperature setting adjustment
Reliability, complexity…
22
Conclusion
Similar to how centralized and decentralized control philosophies are applied in the control of generation and transmission systems, it is expected that the advantages
- f both centralized control and decentralized control be
exploited to achieve the best performance of the smart grid.
23
Acknowledgement
Research is funded by PNNL lab directed research and development (LDRD) program. The project team received support and help from the following PNNL colleagues:
Carl Imhoff Dave Chassin Jason Fuller Chellury Sastry
Questions? Contact:
- Dr. Shuai Lu
Shuai.lu@pnl.gov
25