On site Testing of ultralong DC cables Peter Mohaupt Mohaupt High - - PowerPoint PPT Presentation

on site testing of ultralong dc cables
SMART_READER_LITE
LIVE PREVIEW

On site Testing of ultralong DC cables Peter Mohaupt Mohaupt High - - PowerPoint PPT Presentation

Grand Projects21 On site Testing of ultralong DC cables Peter Mohaupt Mohaupt High Voltage GmbH Austria Sate of the Art DC Test Systems Grand cascaded - called Greinacher or Cockcroft Walton Projects21 + Small footprint


slide-1
SLIDE 1

Grand Projects’21

On site Testing of ultralong DC cables

Peter Mohaupt Mohaupt High Voltage GmbH Austria

slide-2
SLIDE 2

Grand Projects’21

Sate of the Art DC Test Systems

cascaded - called Greinacher or Cockcroft Walton

+

  • Small footprint
  • Low input power
  • Low test current (range mA)
  • No integrated discharging
slide-3
SLIDE 3

Grand Projects’21

Advanced DC Test Systems

called DCChargingDischarging

  • Large footprint
  • Clearances for high voltages (2 times peak voltage)

+

  • High test current (up to 10A)
  • Fast charging
  • Fast discharging
  • Emergency discharge in sec.
  • Integrated or external discharging
slide-4
SLIDE 4

Grand Projects’21

Advanced DC Test Systems - Technology

slide-5
SLIDE 5

Grand Projects’21

Outline Data

Maximum output voltage: 600 kV DC (upgradable to 1200 kV) Maximum load capacitance: 10 µF Maximum charging time (up to max. voltage): 60 min Maximum discharging time: 30 min Emergency discharge time: <10 s Input power (3 phases, 400V): 50 kW Accuracy of output voltage measurement: <5 % Automatic

  • utput

voltage stabilization: <1 % Dimension (l x w x h): 7 x 3 x 5.5 m (ca. 15 x 3 x 10 for 1200 kV system) Total system weight (incl. power supply): 6000 kg (ca. 8000 kg for 1200 kV system)

slide-6
SLIDE 6

Grand Projects’21

Thank you for your attention!